Technical data – Lenze E82MVxxx 2Bxxx User Manual
Page 86

Technical data
General data and operating conditions
l
86
EDK82MV371 DE/EN/FR 7.0
Ambient conditions
Climatic conditions
Storage
IEC/EN 60721−3−1
1K3 (−25 ... +60 °C)
Transport
IEC/EN 60721−3−2
2K3 (−25 ... +70 °C)
Operation
IEC/EN 60721−3−3
3K3 (−20 ... +60 °C)
At temperatures > +40 °C, reduce the rated output
current by 2.5 %/°C.
Site altitude
< 4000 m amsl
Reduce rated output current by 5 %/ 1000 m
above 1000 m amsl.
Electrical
Mains connection AC system
Max. mains voltage range
E82MV251... and E82MV371...
1/N/PE or 2/PE 180 V − 0 % ... 264 V + 0 %
E82MV551... to E82MV222...
3/PE 320 V − 0 % ... 550 V + 0 %
E82MV302... to E82MV752...
3/PE 320 V − 0 % ... 550 V + 0 %
Mains frequency
45 Hz − 0 % ... 65 Hz + 0 %
Mechanical
Vibration resistance
(9.81 m/s
2
= 1 g)
Germanischer
Lloyd
l
General
conditions
acceleration resistant up to 2 g
Mounting conditions
Mounting position
All mounting positions and mounting alignments are permitted
Free spacess
Above:
To the sides
100 mm
100 mm
Dimensions,
^
Chapter "Mechanical installation"
Weights
^
Chapter "Technical data", "Operation with rated power" or "Operation