Safety instructions – Lenze ECSDAxxx User Manual
Page 82

Safety instructions
Thermal motor monitoring
l
82
EDKCSDX064 DE/EN/FR 3.0
Behaviour of the I
2
x t monitoring
Condition
The I
2
x t monitoring is deactivated.
C0066 is set = 0 % and
MCTRL−LOAD−I2XT is set = 0.00 %.
When C0120 = 0 % and C0127 = 0 %, set
controller inhibit.
I
2
x t monitoring is stopped.
The current value in C0066 and at the
MCTRL−LOAD−I2XT output is frozen.
When C0120 = 0 % and C0127 = 0 %, set
controller enable.
I
2
x t monitoring is deactivated.
The motor load is displayed in C0066.
Set C0606 = 3 (off) and C0127 > 0 %.
)
Note!
An error message OC6 or OC8 can only be reset if the I
2
x t load falls
below the set trigger threshold by 5 %.