1 mains connection, Mains connection, Electrical installation – Lenze EVF9383 User Manual
Page 87: Both, the master and the slave must be supplied

Electrical installation
Supply and fan connection at the controller for a mains voltage of 400 V/500V
Mains connection
l
87
EDKVF9383 DE/EN/FR 4.0
5.4.1
Mains connection
ƒ
Both, the master and the slave must be supplied!
BR2
BR2
BR1
BR1
+UG
+UG
-UG
-UG
PE
PE
U
U
V
V
W
W
L1
L1
101
101
102
102
103
103
104
104
L2
L2
L3
L3
PE
PE
L1, L2,
L3
25-30 Nm
M8
221-264 lb-in
L1, L2,
L3
25-30 Nm
M8
221-264 lb-in
PE
15-20 Nm
M6
133-176 lb-in
PE
15-20 Nm
M6
133-176 lb-in
40 mm
40 mm
0
1
9300VEC035
Fig. 5−8
Mains connection example
BR1, BR2
Brake resistor can only be operated with the variants V270 and V300
For connection see System Manual of 9300 vector
0
Master terminals
1
Slave terminals
Fuses and cable cross−sections for the mains supply
Type
Installation to EN 60204−1
Fuse
2)
L1, L2, L3 [mm
2
]
PE [mm
2
]
Master
Slave
Master
Slave
Master
Slave
EVF9381−EVV210
EVF9381−EVV240
EVF9381−EVV270
EVF9381−EVV300
315A
315A
150
2 Ч 50
1)
150
2 Ч 50
1)
95
95
EVF9382−EVV210
EVF9382−EVV240
EVF9382−EVV270
EVF9382−EVV300
315A
315A
150
2 Ч 50
1)
150
2 Ч 50
1)
95
95
EVF9383−EVV210
EVF9383−EVV240
EVF9383−EVV270
EVF9383−EVV300
400 A
400 A
240
2 Ч 95
1)
240
2 Ч 95
1)
150
150
1)
Multiple conductor; both conductors must have the same cross−section
2)
Lenze recommends to use fuses of the gRL utilisation category
Observe the national and regional legislation