3 mechanical installation, Important notes, Mechanical installation – Lenze ECSCExxx User Manual
Page 73
Mechanical installation
Important notes
3
l
73
EDKCSCE040 DE/EN/FR 3.0
3
Mechanical installation
3.1
Important notes
ƒ
ECS power supply modules are provided with IP20 enclosure and can
therefore only be used for installation in control cabinets.
ƒ
If the cooling air contains air pollutants (dust, fluff, grease, aggressive
gases):
–
Take suitable preventive measures , e.g. separate air duct, installation
of filters, regular cleaning.
ƒ
Possible mounting positions
–
Vertical at the mounting plate
–
DC bus connections (X22) at the top
–
Mains connection (X21) at the bottom
ƒ
Maintain the specified clearances (above and below) to other
installations!
–
If the ECSZS000X0B shield mounting kit is used, an additional clearance
is required.
–
Ensure unimpeded ventilation of cooling air and outlet of exhaust air.
–
Several modules of the ECS series can be installed in the control cabinet
next to each other without any clearance.
ƒ
The mounting plate of the control cabinet
–
must be electrically conductive.
–
must not be varnished.
ƒ
In case of continuous vibrations or shocks use shock absorbers.