Troubleshooting and fault elimination – Lenze E82xV113Kxxxxx User Manual
Page 23

Troubleshooting and fault elimination
Fault messages on the keypad or in the parameter setting program Global Drive Control
l
23
EDK82EV113 EN 4.0
Remedy
Cause
Fault
PC
1)
Keypad
ErP0
...
ErP19
a
−
Communication
interruption between
keypad and standard
device
Various
Contact Lenze
FAn1
a
95
Fan failure
(only 8200 motec
3 ... 7.5 kW)
TRIP or warning
configurable in C0608
Fan is defective
Replace fan
FAn1
−
Fan is not connected
Connect fan
Check wiring
H05
a
105
Internal fault
Contact Lenze
id1
a
140
Faulty parameter
identification
Motor is not connected
Connect motor
LP1
a
32
Error in motor phase
(Display when C0597 =
1)
l
Failure of one/several motor
phase(s)
l
Motor current too low
l
Check motor supply cables
l
Check V
min
boost,
l
Connect motor with a corresponding
power or adapt motor with C0599
LP1
182
Error in motor phase
(Display when C0597 =
2)
LU
c
−
DC bus undervoltage
Mains voltage too low
Check mains voltage
Voltage in DC−bus connection too low
Check power supply module
400 V controller is connected to 240 V
mains
Connect controller to correct mains voltage
OC1
a
11
Short circuit
Short circuit
l
Search for cause of short circuit; check
motor cable
l
Check brake resistor and cable to brake
resistor
Capacitive charging current of the
motor cable too high
Use shorter/low−capacitance motor cable
OC2
a
12
Earth fault
Earthed motor phase
Check motor; check motor cable
Capacitive charging current of the
motor cable too high
Use shorter/low−capacitance motor cable
Deactivate earth−fault detection for test
purposes
OC3
a
13
Controller overload
during acceleration or
short circuit
Acceleration time set is too short
(C0012)
l
Increase acceleration time
l
Check drive dimensioning
Defective motor cable
Check wiring
Interturn fault in the motor
Check motor
OC4
a
14
Controller overload
during deceleration
Deceleration time set is too short
(C0013)
l
Increase deceleration time
l
Check dimensioning of the external brake
resistor
OC5
a
15
Controller overload
during steady−state
operation
Frequent and too long overload
Check drive dimensioning
OC6
a
16
Motor overload
(I
2
x t overload)
Motor is thermally overloaded by e.g.
l
impermissible continuous current
l
Check drive dimensioning
l
frequent or too long acceleration
processes
l
Check setting of C0120
OH
a
50
Heatsink temperature
> +85 °C
Ambient temperature is too high
Allow controller to cool and provide better
ventilation
OH
e
−
Heatsink temperature
> +80 °C
Heatsink is very dirty
Clean heatsink
Impermissibly high currents or frequent
and too long acceleration processes
l
Check drive dimensioning
l
Check load, exchange tight, defective
bearings if necessary