Troubleshooting and fault elimination
Fault messages on the keypad or in the parameter setting program Global Drive Control
l
22
EDK82EV113 EN 4.0
3.3
Fault messages on the keypad or in the parameter setting program Global Drive Control
Keypad PC
1)
Fault
Cause
Remedy
noer
0
No fault
−
−
CCr
a
71
System failure
Strong interference injections on the
control cables
Shield control cable
Earth loops in the wiring
Ce0
a
61
Communication error
on AIF
(configurable in C0126)
Faulty transmission of control
commands via AIF
Insert the communication module properly
into the diagnosis terminal
Ce1
a
62
Communication error
on CAN−IN1 with sync
control
CAN−IN1 object receives faulty data or
communication is interrupted
l
Check plug connection of bus
module
ó FIF
l
Check sender
l
Increase monitoring time in C0357/1, if
necessary
Ce2
a
63
Communication error
on CAN−IN2
CAN−IN2 object receives faulty data or
communication is interrupted
l
Check plug connection of bus
module
ó FIF
l
Check sender
l
Increase monitoring time in C0357/2, if
necessary
Ce3
a
64
Communication error
on CAN−IN1 with event
or time control
CAN−IN1 object receives faulty data or
communication is interrupted
l
Check plug connection of bus
module
ó FIF
l
Check sender
l
Increase monitoring time in C0357/3, if
necessary
Ce4
a
65
BUS−OFF
(many communication
errors occurred)
Controller has received too many faulty
telegrams via the system bus and has
been disconnected from the bus
l
Check whether bus termination is
available
l
Check shield connection of the cables
l
Check PE connection
l
Check bus load, reduce the baud rate, if
necessary
Ce5
a
66
CAN time−out
(configurable in C0126)
In case of remote parameterisation via
the system bus (C0370):
Slave does not respond.
Communication monitoring time has
been exceeded
l
Check wiring of the system bus
l
Check system bus configuration
When operating with Application I/O:
Parameter set change−over has been
parameterised incorrectly
In all parameter sets, the "change parameter
set" signal (C0410/13, C0410/14) must be
connected with the same source
When operating with module on FIF:
Internal error
Contact Lenze
Ce6
a
67
System bus (CAN)
function module on FIF
has the "Warning" or
"BUS−OFF" status
(configurable in C0126)
CAN controller signals "Warning" or
"BUS−OFF" status
l
Check whether bus termination is
available
l
Check shield connection of the cables
l
Check PE connection
l
Check bus load, reduce the baud rate, if
necessary
Ce7
a
68
Communication error in
case of remote
parameterisation via
the system bus (C0370)
(configurable in C0126)
Node does not respond or is not
available
l
Check whether bus termination is
available
l
Check shield connection of the cables
l
Check PE connection
l
Check bus load, reduce the baud rate, if
necessary
When operating with Application I/O:
Parameter set change−over has been
parameterised incorrectly
In all parameter sets, the "change parameter
set" signal (C0410/13, C0410/14) must be
connected with the same source
EEr
a
91
External fault (TRIP−SET) A digital signal assigned to the TRIP−SET
function is activated
Check external encoder