5 safety instructions, Safety instructions, Safety engineering – Lenze E94AYAB − SM100 User Manual
Page 7

Safety engineering
Basics
Safety instructions
l
7
EDS94AYAB EN 2.1
1.1.5
Safety instructions
Application as directed
The safety modules SMx (E94AYAx) may only be used together with Lenze drive controllers
of the L−force | 9400 (E94A...) series.
Any other use shall be deemed inappropriate!
Installation/commissioning
}
Danger!
Danger to life through improper installation
Improper installation of the safety engineering systems can cause an
uncontrolled starting action of the drives.
Possible consequences:
ƒ
Death or severe injuries
Protective measures:
ƒ
Safety engineering systems may only be installed and commissioned by
qualified and skilled personnel.
ƒ
All control components (switches, relays, PLC, ...) and the control cabinet
must comply with the requirements of ISO 13849−1 and ISO 138492. This
includes i.a.:
– Switches, relays in IP54 enclosure.
– Control cabinet in IP54 enclosure.
– Please refer to ISO 13849−1 and ISO 138492 for all further requirements.
ƒ
It is essential to use insulated wire end ferrules for wiring.
ƒ
All safety relevant cables outside the control cabinet must be protected, e.g.
by means of a cable duct:
– Ensure that there are no short circuits.
– For further measures see ISO 138492.
ƒ
If an external force acts upon the drive axes, additional brakes are required.
Please observe that hanging loads are subject to the force of gravity!