Safety instructions
Safety instructions for the installation according to UL
l
17
MA_CPCx8xx DE/EN/FR/ES/IT 2.0
2.2
Safety instructions for the installation according to UL
Original − English
Approval
Underwriter Laboratories (UL), UL508 and CSA C22.2 No. 142−M1987, (UL File
Number E236341)
Ratings
ƒ
Input 18 ... 30 V DC , max. 4 A
ƒ
ACCU−Pack and CAPS−Pack: max 0.6 A
ƒ
Max. ambient temperature 50 °C.
ƒ
Optional communication ratings:
–
RS232−Connection: max. 3 A
–
USB−Connection: max. 1 A
–
PS/2−Connection: max. 1 A
–
LAN−Connection: Standard ISDN or RJ45
–
DVI−Connection: max. 1 A
J
Warnings!
Field Wiring Markings
Wiring Terminal MSTB 2,5/3−STF−5,08:
ƒ
Use copper wire only.
ƒ
AWG 18 ... AWG 12 (0.82 mm
2
... 3.3 mm
2
)
ƒ
Torque 5...7 lb−in (0.5 ... 0.6 Nm)
Battery
ƒ
Replace battery with any from the list below, Part No. CR 2450
only. Use of another battery may present a risk of fire or
explosion.
Recommended CR2450 (R/C, BBVC2) types:
Renata Part.no. CR2450N, Sony Corp. part no. CR2450B, Toshiba
part no. CR2450, Varta part no. CR2450, Matsushita part no.
CR2450
ƒ
Battery may explode if mistreated. Do not recharge, disassemble,
dispose of in fire or heat above 100 °C (212 °F).
ƒ
Dispose of used battery according to the regulation of recycling
or waste.