Controls and displays

3

21

Lenze ¯ BA_3231C ¯ 5.0

LED status displays

LED

Interval

Meaning

Color 1 / Color 2
Power

Green

Is ON

constantly

Starting sequence properly completed.
¯

No pending error

¯

Controller is switched on

¯

Supply voltage OK

Yellow

Is ON

constantly

The supply voltage has fallen below the minimum value.

Blinking

(2.0 Hz)

Status after switch−on/restart

Green

Yellow

Blinking

(0.5 Hz)

System clock is not synchronised (missing time
information).
Note:
If the Controller is switched off for longer than two weeks,
the set time information is lost.
¯

The next starting sequence generates a logbook entry
(power LED is blinking green).

¯

Set the current time manually via the »WebConfig«
(parameter 91).

Only for Controller 3241 C

Battery pack (ACCU−PACK) or capacitor pack (CAPS−PACK) is
not fully charged.
The length of the dark bar shows the state of charge:
¯

ACCU/CAPS−PACK almost dead: long dark bar

¯

ACCU/CAPS−PACK almost fully charged: short dark bar

Green

Blinking

(5.0 Hz)

Only for Controller 3241 C

Error status of the battery pack (ACCU−PACK) or capacitor
pack (CAPS−PACK)
UPS function not available, possible cause:
¯

Connection to ACCU/CAPS−PACK interrupted

¯

ACCU/CAPS−PACK not connected, cable break/short
circuit

Green

Yellow

Blinking

(5.0 Hz)

Error

Red

Blinking

(5.0 Hz)

Error:
¯

Fatal error (abort)

¯

SD card not available/not inserted correctly

¯

No operating system licence available

Green

Red

Blinking

(5.0 Hz)

Mains switching required

Status 1 ("busy")

Green

Is ON

constantly

Operating status:
¯

Controller running

¯

PLC project running

Blinking

(0.5 Hz)

Starting sequence of the Controller is active

Green

Yellow

Blinking

(0.5 Hz)

User action required:
¯

Load PLC project (PLC was started, project is not running)

¯

Remove USB stick

Status 2

No response