beautypg.com

Hydro-Logic PS-200 PANEL MOUNT DUAL TDS CONTROLLER/MONITOR User Manual

Page 2

background image

2

7

Thank you for purchasing HM Digital’s PS-200. The PS-200 is a panel mount total dissolved solids (TDS)
controller that monitors and controls levels of TDS in water. The controller has a maximum set point to
help maintain a limit of TDS allowed in the product water, as well as a second sensor to monitor the TDS
level of the feed water. If the TDS level rises to the set point, the controller will activate a warning light,
sound an alarm (optional) and switch the dry contact position from the normal position (to operate a
valve, pump, etc.). Once the TDS level drops below the set point, this will deactivate the light and alarm
and switch the contacts back to the normal position (normally open or closed). NOTE: The IN mode &
sensor does not have an alarm nor control set point. It is a monitor only.

CONTACT INFO

BOX CONTENTS

SPECIFICATIONS

If you have any problems or questions regarding your controller, please contact HM Digital, Inc.

HM Digital, Inc.

[email protected]

5819 Uplander Way

www.tdsmeter.com

Culver City, CA 90230

1-800-383-2777

U.S.A

1. Controller

3. Two sensor cables (grey) 5. Mounting brackets

2. Two sensors (SP-1)

4. Power cord (black)

6. U.S. plug adapter

TDS Range:

0 - 999 ppm (mg/L)

Resolution:

1 ppm

Accuracy:

±2% (of the reading)

Temperature Compensation:

Automatic (ATC) (1-60

o

C)

Calibration:

Manual by trimmer pot calibration screw

Set-Point:

Single point, controlled by on-screen up/down buttons (to any point within the range)

Set-Point Relay:

single, isolated, 2A, Max. 220V, resistive load 100,000 strokes

Relay Control (out sensor only):

The unit will open or close a circuit via dry contacts when the

ppm level of the OUT sensor (aka product water) reaches or exceeds the control setting (simple
switch). It can be used to control a pump, solenoid valve or other device.
Relay Voltage:

5V (the connected device needs its own power source)

Alarm:

Optional steady beep (set by user)

Probe:

½” NPTF bushing

Cable Length:

3 meter (9.8 ft) shielded cable

Display:

Bright tri-color L.E.D.

Power Supply:

110V/230V, ±10% Vac; 50/60Hz

Enclosure:

Front and back with ABS

Environment:

-10 to 50

o

C (4 to 122

o

F); RH max 95% non-condensing

Dimensions:

7.2 x 7.2 x 10.2 cm (2.8 x 2.8 x 4 in.)

Monitor Weight:

476 grams (1 lb 0.8 oz)

THIS PAGE INTENTIONALLY LEFT BLANK