Emergency Stop Safety Relay ESM-BA7..
Maintenace
The device must be checked once per month for proper
function and for signs of tampering and bypassing of the
safety function.
Techn. Data
Operating voltage
AC/DC 24V
Rated supply Voltage
50-60Hz
Permissible deviation
+ / - 10%
Power consumption
DC 24V
AC 24V
approx. 4.5 W approx. 8.5 VA
Control voltage at S11
DC 24V
Control current S11..S14
approx. 250mA
Safety contacts
7 NO contacts
Auxiliary contacts
4 NC contacts
Auxiliary transistor outputs (O1, O2)
DC 24V / 30mA, over current protected
Max. switching voltage
AC 250V
Safety contact breaking capacity
AC:
250V, 2000VA, 8A for ohmic load
(13-14, 23-24, 33-34,43-44, 53-54, 63-64, 73-74)
250V, 3A for AC-15
DC: 50V, 8A for ohmic load
24V, 3A for DC-13
Max. total current through all 7 contacts up to Ta=40°C:
35A
10mm spacing between the devices
20A
no spacing between the devices
Auxiliary contacts braking capacity
AC:
250V, 2000VA, 8A for ohmic load
(81-82, 91-92, 101-102,101-112)
Minimum contact load
24V, 20mA
Contact fuses
6A slow blow or 8A quick-action or 10A gG
Line cross section
0.14 -2.5mm
2
Max. length of control line
1000m at 0.75 mm
2
Contact material
AgSnO
2
Contact service life
mech. approx. 1 x 10
7
, electr. 1 x 10
5
operating cycles
Test voltage
2.5kV (control voltage / contacts)
Rated impulse withstand voltage, leakage path/air gap
4kV
(DIN VDE 0110-1)
Rated insulation voltage
250V
Degree of protection
IP20
Temperature range
-15°C bis +40°C
Degree of contamination
2
(DIN VDE 0110-1)
Overvoltage category
3
(DIN VDE 0110-1)
Weight
approx.
350g
Mounting
DIN rail according to EN 60715TH35
Note:
Additional data can be requested from the manufacturer for
applications that deviate from these conditions.
Safety
Characteristics
According to
EN ISO 13849-1
The device is certified according to EN ISO 13849-1 up to a
Performance Level of PL e.
Device cannot be switched on again after an emergency
stop:
•
Check whether the emergency stop circuit was closed
again.
•
Was the start button opened before closing of the emer-
gency stop circuit (with manual start)?
•
Is the feedback loop closed?
If the fault still exists, perform the steps listed under
“Commissioning Procedure”.
If these steps do not remedy the fault either, return the
device to the manufacturer for examination.
Opening the device is impermissible and will void the
warranty.
Device does not switch on:
•
Check the wiring by comparing it to the wiring diagrams.
•
Check the safety switch used for correct function and
adjustment.
•
Check whether the emergency stop circuit is closed.
•
Check whether the start button (with manual start) is
closed.
•
Check the operating voltage at A1 and A2.
•
Is the feedback loop closed?
What to Do in
Case of a Fault?
The device is otherwise maintenance free, provided that it
was installed properly.
Safety characteristics according to EN ISO 13849-1 for all variants of ESM-BA7
Load (DC-13; 24V)
<= 0.1A
<= 1A
<= 2A
T10d [years]
20
20
20
Category:
4
4
4
PL
e
e
e
PFHd [1/h]
2.47E-08
2.47E-08
2.47E-08
nop [cycle / year]
<= 500.000
<= 350.000
<= 100.000