Emergency Stop Safety Relay ESM-BA7..

Maintenace

The device must be checked once per month for proper
function and for signs of tampering and bypassing of the
safety function.

Techn. Data

Operating voltage

AC/DC 24V

Rated supply Voltage

50-60Hz

Permissible deviation

+ / - 10%

Power consumption

DC 24V

AC 24V

approx. 4.5 W approx. 8.5 VA

Control voltage at S11

DC 24V

Control current S11..S14

approx. 250mA

Safety contacts

7 NO contacts

Auxiliary contacts

4 NC contacts

Auxiliary transistor outputs (O1, O2)

DC 24V / 30mA, over current protected

Max. switching voltage

AC 250V

Safety contact breaking capacity

AC:

250V, 2000VA, 8A for ohmic load

(13-14, 23-24, 33-34,43-44, 53-54, 63-64, 73-74)

250V, 3A for AC-15

DC: 50V, 8A for ohmic load

24V, 3A for DC-13

Max. total current through all 7 contacts up to Ta=40°C:

35A

10mm spacing between the devices

20A

no spacing between the devices

Auxiliary contacts braking capacity

AC:

250V, 2000VA, 8A for ohmic load

(81-82, 91-92, 101-102,101-112)
Minimum contact load

24V, 20mA

Contact fuses

6A slow blow or 8A quick-action or 10A gG

Line cross section

0.14 -2.5mm

2

Max. length of control line

1000m at 0.75 mm

2

Contact material

AgSnO

2

Contact service life

mech. approx. 1 x 10

7

, electr. 1 x 10

5

operating cycles

Test voltage

2.5kV (control voltage / contacts)

Rated impulse withstand voltage, leakage path/air gap

4kV

(DIN VDE 0110-1)

Rated insulation voltage

250V

Degree of protection

IP20

Temperature range

-15°C bis +40°C

Degree of contamination

2

(DIN VDE 0110-1)

Overvoltage category

3

(DIN VDE 0110-1)

Weight

approx.

350g

Mounting

DIN rail according to EN 60715TH35

Note:
Additional data can be requested from the manufacturer for
applications that deviate from these conditions.

Safety
Characteristics
According to
EN ISO 13849-1

The device is certified according to EN ISO 13849-1 up to a
Performance Level of PL e.

Device cannot be switched on again after an emergency
stop:

Check whether the emergency stop circuit was closed
again.

Was the start button opened before closing of the emer-
gency stop circuit (with manual start)?

Is the feedback loop closed?

If the fault still exists, perform the steps listed under
“Commissioning Procedure”.
If these steps do not remedy the fault either, return the
device to the manufacturer for examination.
Opening the device is impermissible and will void the
warranty.

Device does not switch on:

Check the wiring by comparing it to the wiring diagrams.

Check the safety switch used for correct function and
adjustment.

Check whether the emergency stop circuit is closed.

Check whether the start button (with manual start) is
closed.

Check the operating voltage at A1 and A2.

Is the feedback loop closed?

What to Do in
Case of a Fault?

The device is otherwise maintenance free, provided that it
was installed properly.

Safety characteristics according to EN ISO 13849-1 for all variants of ESM-BA7

Load (DC-13; 24V)

<= 0.1A

<= 1A

<= 2A

T10d [years]

20

20

20

Category:

4

4

4

PL

e

e

e

PFHd [1/h]

2.47E-08

2.47E-08

2.47E-08

nop [cycle / year]

<= 500.000

<= 350.000

<= 100.000