2-Hand Safety Relay, Series ESM-2H2..

Maintenance

What to Do in
Case of a Fault?

Once per month, the device must be checked for proper
function and for signs of tampering and bypassing of the
safety function (to do this, check the wiring of the device
and activate the emergency stop function. Check the delay
time).

The device is otherwise maintenance free, provided that it
was installed properly.

Note:

Additional data can be requested from the manufacturer for
applications that deviate from these conditions.

Safety
Characteristics
According to
EN ISO 13849-1

The device is certified according to EN ISO 13849-1 up to a
Performance Level of PL e.

Techn. Data

Operating voltage

ESM-2H201

ESM-2H202

ESM-2H203

AC/DC 24V

AC 115V

AC 230V

Rated supply frequency

AC: 50-60Hz

Permissible deviation

+/- 10%

Power consumption

DC 24V

AC 230V

approx. 1.5W approx. 3.7VA

Control voltage at S12-S13 and at S22-S23

DC 24V

Control current (both switches)

approx. 2 x 40mA

Release time for the safety relays after release of a button

< 20ms

Response delay after actuation of the buttons

< 20ms

Syncronization time

< 0.5s

Safety contact configuration

2 NO contacts

Max. switching voltage

AC 250V

Safety contact breaking capacity

AC:

250V, 2000VA, 6A for ohmic load,

230V, 3A for AC-15

DC:

24V, 192W, 6A for ohmic load;

24V, 3A for DC-13

Max. total current through all contacts:

12 A

Minimum contact load

24V, 20mA

Contact fuses

6A slow-blow or 8 A quick-action or 10A gG

Line cross section

0.14 - 2.5mm

2

Max. length of control line

1000m with 0.75mm

2

Contact material

AgSNO

2

Contact service life

mech. approx. 1 x 10

7

, electr. 1 x 10

5

operating cycles

Test voltage

2.5kV (control voltage/contacts)

Rated impulse withstand voltage, leakage path/air gap

4kV

(DIN VDE 0110-1)

Rated insulation voltage

250V

Degree of protection

IP20

Degree of contamination

2

(DIN VDE 0110-1)

Overvoltage category

3

(DIN VDE 0110-1)

Temperature range

DC 24V:

-15°C to +60°C

AC 230V/115V/24V:

-15°C to +40°C

Weight

ca. 230g

Mounting

DIN rail according to EN 60715TH35

Safety characteristics according to EN ISO 13849-1 for all variants of ESM-2H2..

Load (DC-13; 24V)

<= 0,1A

<= 1A

<= 3A

T10d [years]

20

20

20

Category:

4

4

4

PL

e

e

e

PFHd [1/h]:

1,2E-08

1,2E-08

1,2E-08

nop [cycle / year]

<= 400.000

<= 100.000

<= 22.500

What to Do in
Case of a Fault?

If the fault still exists, perform the steps listed under
“Commissioning Procedure”.

If these steps do not remedy the fault either, return the
device to the manufacturer for examination.

Opening the device is impermissible and will void the
warranty.

Device does not switch on:

Check whether the 2-hand button of correct function.

Check whether the wiring.

Check the supply voltage on A1 and A2

Is the feedback loop closed?