Hand safety relay, series esm-2h2, User information – EUCHNER ESM-2H2 Series User Manual
Page 3
User Information
3
EUCHNER GmbH + Co. KG Kohlhammerstraße 16 D-70771 Leinfelden-Echterdingen Tel. +49/711/75 97-0 Fax +49/711/75 33 16 www.euchner.de [email protected]
2-Hand Safety Relay, Series ESM-2H2..
Maintenance
What to Do in
Case of a Fault?
Once per month, the device must be checked for proper
function and for signs of tampering and bypassing of the
safety function (to do this, check the wiring of the device
and activate the emergency stop function. Check the delay
time).
The device is otherwise maintenance free, provided that it
was installed properly.
Note:
Additional data can be requested from the manufacturer for
applications that deviate from these conditions.
Safety
Characteristics
According to
EN ISO 13849-1
The device is certified according to EN ISO 13849-1 up to a
Performance Level of PL e.
Techn. Data
Operating voltage
ESM-2H201
ESM-2H202
ESM-2H203
AC/DC 24V
AC 115V
AC 230V
Rated supply frequency
AC: 50-60Hz
Permissible deviation
+/- 10%
Power consumption
DC 24V
AC 230V
approx. 1.5W approx. 3.7VA
Control voltage at S12-S13 and at S22-S23
DC 24V
Control current (both switches)
approx. 2 x 40mA
Release time for the safety relays after release of a button
< 20ms
Response delay after actuation of the buttons
< 20ms
Syncronization time
< 0.5s
Safety contact configuration
2 NO contacts
Max. switching voltage
AC 250V
Safety contact breaking capacity
AC:
250V, 2000VA, 6A for ohmic load,
230V, 3A for AC-15
DC:
24V, 192W, 6A for ohmic load;
24V, 3A for DC-13
Max. total current through all contacts:
12 A
Minimum contact load
24V, 20mA
Contact fuses
6A slow-blow or 8 A quick-action or 10A gG
Line cross section
0.14 - 2.5mm
2
Max. length of control line
1000m with 0.75mm
2
Contact material
AgSNO
2
Contact service life
mech. approx. 1 x 10
7
, electr. 1 x 10
5
operating cycles
Test voltage
2.5kV (control voltage/contacts)
Rated impulse withstand voltage, leakage path/air gap
4kV
(DIN VDE 0110-1)
Rated insulation voltage
250V
Degree of protection
IP20
Degree of contamination
2
(DIN VDE 0110-1)
Overvoltage category
3
(DIN VDE 0110-1)
Temperature range
DC 24V:
-15°C to +60°C
AC 230V/115V/24V:
-15°C to +40°C
Weight
ca. 230g
Mounting
DIN rail according to EN 60715TH35
Safety characteristics according to EN ISO 13849-1 for all variants of ESM-2H2..
Load (DC-13; 24V)
<= 0,1A
<= 1A
<= 3A
T10d [years]
20
20
20
Category:
4
4
4
PL
e
e
e
PFHd [1/h]:
1,2E-08
1,2E-08
1,2E-08
nop [cycle / year]
<= 400.000
<= 100.000
<= 22.500
What to Do in
Case of a Fault?
If the fault still exists, perform the steps listed under
“Commissioning Procedure”.
If these steps do not remedy the fault either, return the
device to the manufacturer for examination.
Opening the device is impermissible and will void the
warranty.
Device does not switch on:
•
Check whether the 2-hand button of correct function.
•
Check whether the wiring.
•
Check the supply voltage on A1 and A2
•
Is the feedback loop closed?