Test, Enable walk test mode, Occupancy/vacancy sensor – ETC Echo Occupancy-Vacancy Sensor User Manual
Page 9
E T C I n s t a l l a t i o n G u i d e
Occupancy/Vacancy Sensor
Page 9 of 10 Occupancy/Vacancy Sensor Install Guide
Test
Occupancy/Vacancy Sensors offer a Walk Test mode which shortens the
vacancy timer to 10 seconds, allowing for simple and quick verification of the
sensors coverage and range in the installed space.
Enable Walk Test Mode
Step 1: Prepare the site for configuration.
a: Make certain the sensor and lighting loads are powered and
connected for control by the Echo controller.
b: You will need direct access to the Occupancy/Vacancy Sensor in
order to place it into Walk Test mode.
Step 2: Press the [Walk Test] button on the front of the sensor to enable the
Walk Test feature at the sensor. A green LED will begin to flash,
indicating Walk Test is enabled and the vacancy/no vacancy
occupancy timer will be shortened to 10 seconds.
Step 3: Move throughout the space including corners and areas that may
specifically be obscured from line of sight to the sensor. Each time the
sensor detects movement, the lens will illuminate red.
Step 4: Adjust the lens masking, if installed, blocking certain areas of the
installed space from sensor detection.
Step 5: Walk Test mode will automatically exit after five minutes from the time
it was enabled. To manually exit the Walk Test mode, press either of
the buttons on the sensor.
Auxiliary
button
Walk Test
button
Walk-Test mode automatically exits and the sensor
returns to normal operation after 5 minutes and can
be manually terminated early by pressing the
[Walk Test] button.