18
Power converts to 24
VDC in control panel
IV
SPECIFICATIONS
General Specs
• Input Power
120/240 VAC (50/60Hz.) 1 Phase
240 VA max. power
• Electrical Load
2 AMPS MAX
• Panel Dimensions
24” x 36” (610mm x 914mm) – 2 Monitor OCP
20” x 24” (508mm x 610mm) – 1 Monitor OCP
• Panel Weights
Approx. 100 lbs. (45 kg) – 2 Monitor OCP
Approx. 80 lbs. (36 kg) – 1 Monitor OCP
• Operating Temperature Range
+14
o
F to +140
o
F (-10
o
C to +60
o
C)
UL Product Marking
• UL Listed and Labeled (Class 1, Division 2)
V
MAINTENANCE
Monthly Inspection and Maintenance
1.
Check all terminal blocks and connections for being properly taut to 4.5 – 7.1 in-lbs (0.508 – 0.802
Nm).
2.
Check all contact blocks and operators for functionality. If there are loose connections tighten them. If
a contact block is not functioning properly, replace it.
3.
Check all light bulbs on outside of the panel. If any are burnt out, replace the bulb.
4.
Check for proper operation of system overall. Please refer to the Troubleshooting section if you are
experiencing problems.
Attention:
When cycling the monitor through the motions (up, down, left, right), be
sure to exercise the system a minimum of 2 (two) complete cycles. This will help redistribute
the grease inside the monitor for improved operation and extended durability.