III SPECIFICATIONS
General Specs
Input Power
120/240 VAC (50/60Hz.)
440/480 VAC (50/60 Hz.)
500 VA max. Power
Electrical Load
5 AMPS MAX at 120/240 VAC
1 AMP MAX at 440/480 VAC
Fused Output Power
24 VDC – 5 AMPS MAX
120 VAC – 3 AMPS MAX
Panel Dimensions
24” X 30” (610 mm x 762 mm)
Panel Weight
Approx. 100 lbs (45 kg)
Operating Temperature Range +14
o
F to +158
o
F (-10
o
C to +70
o
C)
UL and ATEX Product Marking (if ordered)
UL Inspected and Labeled (Class 1, Division 2)
CE ATEX certification available upon advanced request
IV OPERATING INSTRUCTIONS
This control panel has one ON/OFF 2-position selector switch. Move it to the ON position so the pilot light
illuminates, showing the panel is now powered up, and ready for associated monitor operation.
V MAINTENANCE
Monthly Inspection and Maintenance
1. Check the indicator light and replace bulb if it’s not operable.
2. Confirm that all terminal blocks and connections are properly taut to 4.5 – 7.1 in-lbs. (0.508 – 0.802
Nm).
3. Check for proper operation of the system overall, if there are problems with the system please refer to
the Troubleshooting section for help.