Step 7. operational settings – Elkhart Brass Cobra EXM Quick Install Guide User Manual
Page 3
CALIBRATE HORIZONTAL
ENTER/EXIT SETUP MODE
CALIBRATE VALVE
On the Handheld,
press and hold
FOG & STREAM
buttons for 5 sec.
(AUX & PRESET on
Joystick). Blue
Status LED on
monitor & yellow
LED on controller
will be lit.
Press and release
FOG & STREAM
(AUX & PRESET on
Joystick) one time.
LEDs will turn off.
You will need to
calibrate the
valve before use.
While you are
NOT in setup
mode, place the
valve in a half
open position,
then press and
hold PRESET &
CLOSE until
calibration
begins. The valve
will automatically
start to calibrate
itself.
Aim monitor at
center forward
“zero” position.
Hold PRESET, then
press and release
LEFT or RIGHT.
The Status LED on
monitor should
blink and return to
solid. Release
PRESET button.
VERTICAL TRAVEL LIMITS
HORIZONTAL TRAVEL LIMITS
CALIBRATE VERTICAL
Move monitor to
the left limit and
press CLOSE.
Move monitor to
the right limit and
press OPEN.
Maximum travel
limits will allow
+175° from the
calibrated “zero”
position in either
direction.
Aim monitor at the
uppermost limit of
travel. Hold
PRESET, then press
and release UP.
The Status LED on
monitor should
blink and return to
solid. Release
PRESET button.
NOTE: This
calibration point
is factory set at
90° (straight up).
Upper:
Move monitor to
highest point of
travel. Hold
STREAM, then
press UP, and
release both.
Lower:
Move monitor to
lowest point of
travel. Hold
STREAM, then
press DOWN, and
release both.
STOW POSITION
KEEP-OUT ZONES
MONITOR MOTOR SPEEDS
Lower Left:
Move to top right
corner of the
lower left zone,
hold PRESET,
press CLOSE,
and release both.
Lower Right:
Move to top left
corner of the
lower right zone,
hold PRESET,
press OPEN, and
release both.
Pressing the OSC
button will cycle
through the
monitor speed
options:
LEDs - Vert / Horz
0 - Fast / Fast
1 - Slow / Fast
2 - Fast / Slow
3 - Slow / Slow
Move monitor to
desired position,
then press FOG
and OSC at the
same time to store
a stow position.
Stow position must
be within allowed
limits of travel.
Step 7. Operational Settings
NOTE: (R) This step is required. (O) This step is optional.
OSC
OPEN
PRESET
CLOSE
(R)
(R)
R
L
Lower Left Zone:
Top right corner
Lower Right Zone:
Top left corner
0°
Right Travel Limit
*Monitor in drawing may differ from actual monitor
Left Travel Limit
Lower Left
Zone
Lower Right
Zone
(O)
(O)
(O)
(O)
0
1
2
3
(O)
(O)
90°
STATUS
POWER
STREAM
PRESET
OPEN
AUX
OSC
OPEN
CLOSE
OSC
FOG
STREAM
PRESET
OPEN
OSC
AUX
90°
-45° to +90° max.
(+120° with extended
travel enabled)
0°
STREAM
AUX
OSC