I OPERATING INSTRUCTIONS

A. Portable Mode


1. Whenever monitor is operated in portable mode, the unit must be anchored with the safety chain provided.

The chain should be hooked to the eye bolt at the front of the monitor and looped around a rigid stationary
object such as a stake, parking meter, fence post, etc. located in front of the monitor. Attach snap hook to a
chain link.

2. Be sure ground spikes are sharp and adjusted so that all spikes contact the ground surface.

3. The Elkhart portables are designed to have the supply hose lines attached with the manifold inlets to the rear

of the monitor discharge. Do not position the inlet manifold to attach the supply hoses from the front of the
unit, as such practice will increase the possibility of the monitor sliding on smooth surfaces. To minimize the
possibility of charged hose lines moving the monitor, supply hoses should be kept straight in line with their
respective inlet ports for a distance of 10 feet behind the inlet manifold.

4. The model 8287 monitor has safety stops to prevent vertical stream travel below 25

⁰ in order to insure

monitor stability when used in portable mode. These safety stops can be released to allow operation below
25

⁰, but should be released only when monitor is secured in appropriate truck mount bracket (see section B).

5. The horizontal travel should not exceed 45

⁰ to either side of the straight-ahead stream position in order to

minimize the possibility of the monitor sliding sideways.

6. Inadvertent horizontal stream movement is prevented by the use of a locking device. The 8287 has a plunger

type lock acting on the horizontal drive pinion. This device should be kept in the locked position except when
horizontal stream position is being changed.

7. The maximum safe operating pressure for the 8287 unit is 150 PSI (10 BAR). The maximum allowable flow

rate for the model 8287 is 1250 GPM (4732 LPM).


B. Truck Mounted Mode


1. Fixtures are available to allow for storage and operation of the Elkhart portable monitors in a truck mounted

mode. Use mounting fixture #8290 for the #8287 monitor. The mounting fixture should be located on the
apparatus to allow effective direction of the stream without interfering with other apparatus mounted
equipment such as flood lights, booster reels, etc.

2. The fixture must be securely attached to a rigid structure capable of safely withstanding a nozzle reaction

force of 700 lbs.

3. The #8287 monitor is attached to the #8290 fixture by placing the five ground spikes on the rubber pads of the

top plate. The center port of the inlet manifold must extend between the two closely spaced clamping posts.
The monitor should be positioned so that the two hook-type clamps can be swung over the lateral support
legs. Swing the rear clamp bar over the center portion of the inlet manifold and place hook end of clamp bar
around the clamping post and under knob. Securely tighten knob.

4. a. When operated in the truck mount fixture, the primary horizontal positioning of the stream must be

accomplished before water is flowing by rotating fixture top plate. To rotate top plate, pull up on locking
device knob and turn plate to desired position. Next, further rotate plate so locking device pin drops into
closest lock hole.