VI. SPECIFICATIONS ±10% (Physical/Electrical)
A. Handheld Controller
Input power
Li-Ion 3.7V
Expected battery life 3.5 hours with continuous RF Transmission
Real time clock & calendar
(RTCC) battery life 2 years without continuous power and 15 years with continuous power
Electrical Load
0.5 AMPS
RF power output
Meets FCC part 15 requirements for license free operation
Transmitter dimensions
7 17/32” x 3 19/32” x 2 ¼”
Transmitter weight
1.2 lbs
Operating temperature range -14
o
F to +150
o
F
Environmental Rating
NEMA 4
FCC ID
KQL-2510100
Charge Time
Approx. 4 hours
B. Monitor Controller
Input power
12/24 VDC (11 VDC to 27 VDC)
Electrical Load
See Table 1 Below
RF power output
Meets FCC part 15 requirements for license free operation
Operating temperature range -14
o
F to +150
o
F
Environmental Rating
NEMA 4
FCC ID
KQL-2510100
Monitor Left/Right
Up/Down Nozzle
Run Current
5 A
5 A
0.5 A
Stall Current
70 A
70 A
N/A
Current Trip Point
12 A
12 A
4 A
Table 2: Motor Current Specifications
C. Battery
Input power
12.8V, 13.2 Ah Li-Ion
Maximum Charge Rate
3.0A
Maximum Discharge Rate
26.0A (Can be charged and discharged at the same time)
Life Cycle
2000 Cycles
Operating Time
1.5 hours
Charge Time
Approx. 6.2 hours
D. Base Unit
Dimensions (H x W x L)
30” x 22” x 60”
Weight
Approx. 86 lbs
E. Waterway
Dimensions (H x W x L)
32” x 13” x 93”
Main Pipe OD
4”
Extension Pipe OD
3.5”
Intake
2.5” Female Swivel
Extension Length
7’ 9” to 15’ with monitor
Weight
Approx. 81 lbs