Det-Tronics X7050 xWatch Industrial Video Surveillance Camera User Manual
Page 6
3.1
95-8600
4
important saFety notes
WarnIng
Do not open the camera assembly in a hazardous
area when power is applied. The device contains
no serviceable components and should not be
opened, except during installation and setup.
CautIon
The wiring procedures in this manual are intended
to ensure proper functioning of the device under
normal conditions. However, because of the
many variations in wiring codes and regulations,
total compliance to these ordinances cannot be
guaranteed. Be certain that all wiring complies
with the NEC as well as all local ordinances. If
in doubt, consult the authority having jurisdiction
before wiring the system.
attentIon
Observe precautions for handling electrostatic
sensitive devices. Do not plug the camera module
into the base with power applied.
installation
CautIon
Installation and wiring of the Model X7050 Camera
should be performed only by qualified personnel.
PrOTECTIOn AgAInsT MOIsTurE DAMAgE
It is important to take proper precautions during
installation to ensure that moisture will not come in contact
with the electrical connections or components of the
system. The integrity of the system regarding moisture
protection must be maintained for proper operation and
is the responsibility of the installer.
If conduit is used, drains must be installed at water
collection points to automatically drain accumulated
moisture. Conduit breathers should be installed at upper
locations to provide ventilation and allow water vapor to
escape. At least one breather should be used with each
drain.
Conduit raceways should be inclined so that water will
flow to low points for drainage and will not collect inside
enclosures or on conduit seals. If this is not possible,
install conduit drains above the seals to prevent the
collection of water or install a drain loop below the camera
with a conduit drain at the lowest point of the loop.
Conduit seals are not required for compliance with
explosion-proof installation requirements, but are highly
recommended to prevent water ingress in outdoor
applications. Units with M25 thread must use an IP66
washer to prevent water ingress.