DC SHUNT FOR DIGITAL AMMETERS AND MULTIMETER
Install shunt for digital DC current measurement:
Caution: The shunt must be installed in the negative line to avoid damage 
to the meter. Positive voltage applied to digital meter terminals #4 and #5 
will cause damage to the meter.
An	external	shunt	is	supplied	with	360	panels	that	include	a	DC	Digital
Ammeter or Multimeter. Install the shunt at any point in the DC negative 
feed line to the panel. Mount it close to the panel to keep the sense wires 
that run from the shunt to the meter short. Short sense wires minimize 
voltage loss and interference, and result in the most accurate metering. 
Mounting it close to the battery bank may make it easier to include more 
circuits,	such	as	24-hour	circuits,	in	the	metering.	Wire	runs	greater	than	50	
feet	using	#16	AWG	wire	may	produce	errors	up	to	1%.	Use	16	AWG	wire	
for sense connections.
For more information go to www.bluesea.com
TO BATTERY
SWITCH
TO BATTERY
SWITCH
DO NOT
INSTALL SHUNT
IN POSITIVE
FROM NEGATIVE
DC DISTRIBUTION
(ALL LOADS AND
SOURCES)