Blue Sea Systems 1408 M-Series Dual Circuit Plus, Main + 3 Position CLB Vertical User Manual
Page 10

8
For more information go to www.bluesea.com
DC SHUNT FOR ANALOG AMMETERS
Install shunt for analog DC current measurement:
An	external	shunt	is	supplied	with	360	panels	that	include	a	DC	analog	
ammeter. Install the shunt at any point in the DC positive or negative, prefer-
ably in the most direct high current path (do not reroute the direct current 
path to accommodated shunt placement). Mount shunt close to the panel 
to keep the sense wires that run from the shunt to the meter short. Short 
sense wires minimize voltage loss and result in the most accurate metering. 
Mounting the shunt close to the battery bank may make it easier to include 
more	circuits,	such	as	24-hour	circuits,	in	the	metering.	Wire	runs	up	to	50	
feet	using	#16	AWG	wire	may	produce	errors	up	to	1%.	Use	16	AWG	wire	
for	sense	connections	up	to	50	feet	in	length;	use	higher	gauge	wire	for	
longer	wire	runs.	There	should	be	a	1	Ampere	fuse	in	both	sense	wires	near	
the shunt terminals. 
Notes: 
1.	Where	a	long	run	is	required	between	meter	and	shunt,	minimize	
 interference by twisting the sense wires together.
2. If the shunt is installed in the negative feed line, no fuses are required. 