• Programming Modes

For ease of programming, the DCR-WEB modes are grouped into phases of an

application setup. The phases are:

1)

Operation

2)

Filtering

3)

Outputs

4)

Calibration

5)

Utilities

This order should be followed for setting up any application.

Operation

The operation modes are used to perform basic initialization of the DCR-WEB.

MODE

DESCRIPTION PARAMETERS

EXPLANATION

SENSITIV

Sensitivity

Units = %
Range = 0 - 100 %
Default = 50

BLANKING Blanking

Units = Inches
Range = 6 - 99
Default= 6 in.

PULSES

Pulses

Range = 1-20
Default = 10

• Higher number of pulses allows the sensor to detect smaller objects better.

Adjust responsiveness to outside
stimuli, KEEP AS LOW AS
POSSIBLE,

Sets a dead zone in front of the
transducer where echoes are
ignored.

Sets the number of times the
transducer is pulsed for each
ultrasonic burst. Adjusts the
strength of the transmitting
signal.