ACCESSORY USAGE GUIDELINE

ACCESSORY

REQUIRED FOR

LOW-AMBIENT

APPLICATIONS

(BELOW 55°F)

REQUIRED FOR

LONG-LINE

APPLICATIONS*

(OVER 50 FT)

REQUIRED FOR

BURIED LINE

APPLICATIONS†

(OVER 3 FT)

REQUIRED FOR

SEA COAST

APPLICATIONS

(WITHIN 2 MILES)

Crankcase Heater

Yes

Yes

Yes

No

Evaporator Freeze Thermostat

Yes

No

No

No

Winter Start Control

Yes‡

No

No

No

Accumulator

No

No

Yes

No

Compressor Start Assist

Capacitor and Relay

Yes

Yes

Yes

No

Low-Ambient Controller,

MotorMaster® Control,

or

Low-Ambient Pressure Switch

Yes

No

No

No

Wind Baffle

See Low-Ambient Instructions

No

No

No

Coastal Filter

No

No

No

Yes

Support Feet

Recommended

No

No

Recommended

Liquid-Line Solenoid Valve

or

Hard Shutoff TXV

No

See Long-Line

Application

Guideline

Yes

No

Ball Bearing Fan Motor

Yes**

No

No

No

* For tubing line sets between 50 and 175 ft, refer to the Application Guideline and Service Manual for Residential Split-System Air Conditioners and Heat Pumps using

R-410A Refrigerant.

† For buried line applications, refer to Residential Split System Buried-Line Application Guideline.
‡ Only when low-pressure switch is used.
** Required for Low-Ambient Controller (full modulation feature) and MotorMaster® Control only.

—5—