Page 33

SECTION -
3120861
– JLG Lift –
-7
5. 4 FLASHES - Motor Permanently High.
 - Direction contactor welded. (Point ‘A’ within 6V of B + ve in neutral).
 - Drive inhibited.
 - Flashes in neutral until fault is cleared. 
6. 5 FLASHES - Motor Neither Low Nor High. (Open Circuit)
 - Direction contactors (or line contactor) did not close.
 - Point ‘A’ not within 6V of B + ve after 500mS.
 - Drive inhibited.
 - Flashes until fault is cleared, when contactor closes. 
NOTE: If recycling to neutral does not clear the fault, then the fail-safe is due to an S/C contactor coil and the key switch must
be recycled (and coil replaced).
Figure 2-1. Sevcon Controller Troubleshooting Flow Charts. (Sheet 2 of 4).