JLG 45e Service Manual User Manual
Page 33

SECTION -
3120861
– JLG Lift –
-7
5. 4 FLASHES - Motor Permanently High.
- Direction contactor welded. (Point ‘A’ within 6V of B + ve in neutral).
- Drive inhibited.
- Flashes in neutral until fault is cleared.
6. 5 FLASHES - Motor Neither Low Nor High. (Open Circuit)
- Direction contactors (or line contactor) did not close.
- Point ‘A’ not within 6V of B + ve after 500mS.
- Drive inhibited.
- Flashes until fault is cleared, when contactor closes.
NOTE: If recycling to neutral does not clear the fault, then the fail-safe is due to an S/C contactor coil and the key switch must
be recycled (and coil replaced).
Figure 2-1. Sevcon Controller Troubleshooting Flow Charts. (Sheet 2 of 4).
This manual is related to the following products: