Bryant 764A User Manual
Page 6
Table 1 — Physical Data
UNIT 564A AND 764A
024
030
036
042
048
060
OPERATING WEIGHT (lb)
222
236
250
297
310
350
COMPRESSOR TYPE
Reciprocating
REFRIGERANT
R-22
Charge (lb)
2.8
3.9
4.7
4.4
6.1
7.5
REFRIGERANT METERING DEVICE
Acutrol™ System
CONDENSER COIL
Copper Tubes, Aluminum Plate Fins
Rows...Fins/in.
1...17
1...17
2...17
1...17
2...17
2...17
Total Face Area (sq ft)
6.7
7.9
6.2
11.1
8.6
10.7
CONDENSER-FAN MOTOR
Propeller
Cfm
1600
2000
2000
2600
2600
2800
Nominal Rpm
825
1100
1100
1100
1100
1100
Motor Hp
1
⁄
8
1
⁄
4
1
⁄
4
1
⁄
4
1
⁄
4
1
⁄
4
Diameter (in.)
20
20
20
20
20
20
EVAPORATOR COIL
Copper Tubes, Aluminum Plate Fins
Rows...Fins/in.
2...15
3...15
3...15
3...15
3...15
4...15
Total Face Area (sq ft)
2.8
2.8
3.1
3.9
4.3
4.9
EVAPORATOR-FAN MOTOR
Direct Drive
Blower Motor Size (in.)
10 x 8
10 x 8
10 x 8
10 x 9
10 x 9
10 x 10
Nominal Cfm
800
1000
1200
1400
1600
2000
Rpm Range
550-1000
550-1000
800-1050
800-1050
1000-1100
950-1100
Number of Speeds
3
3
3
3
2
3*
Factory Speed Setting
Low
Med
Low
Med
Low
Low
Motor Hp
1
⁄
4
1
⁄
4
1
⁄
2
1
⁄
2
3
⁄
4
1
CONNECTING DUCT SIZES
Round
Square
Supply Air (in.)
14
13.9 x 13.9
Return Air (in.)
14
13.9 x 27.8
FIELD-SUPPLIED RETURN AIR FILTER†
Throwaway (in.)
24 x 24
24 x 24
24 x 24
24 x 24
24 x 30
24 x 30
*460-v motors are 2-speed only.
†Required filter sizes shown are based on the ARI (Air Conditioning and Refrigeration Institute)
rated airflow at a velocity of 300 ft/min for throwaway type or 450 ft/min for high capacity type.
Recommended filters are 1-in. thick.
If the installation requires draining the condensate water
away from the unit, install a field-supplied 2-in. trap using
3
⁄
4
-in. OD tubing or piping to ensure proper drainage. See
Fig. 8A and 8B. Make sure that the outlet of the trap is at
least one in. lower than the unit drain pan condensate con-
nection to prevent the pan from overflowing. Connect a drain
tube using a minimum of
3
⁄
4
-in. PVC,
3
⁄
4
-in. CPVC, or
3
⁄
4
-in.
copper pipe (all field-supplied). Do not undersize the tube. Pitch
the drain tube downward at a slope of at least 1 inch in every
10 ft of horizontal run. Be sure to check the drain tube for
leaks. Prime trap at the beginning of cooling season start-up.
Allowable glues for condensate trap connection are: Stand-
ard ABS, CPVC, or PVC cement.
B. Field-Duct Connections
NOTE:
The design and installation of the duct system must
be in accordance with the standards of NFPA for the instal-
lation of nonresidence-type air conditioning and ventilating
systems, NFPA 90A or residence-type, NFPA 90B, and/or
local codes and ordinances.
Units have duct flanges on the supply- and return-air open-
ings on the side of the unit. See Fig. 2-4 for connection sizes
and locations.
CONDENSATE DRAIN HOLE
Fig. 7 — Condensate Connection Details
Fig. 8A — Condensate Trap (Using Tubing)
Fig. 8B — Condensate Trap (Using PVC Piping)
—6—