BASE UNIT DIMENSIONS – 582A048-060
FLUE HOOD
REQ'D CLEARANCES FOR OPERATION AND SERVICING. in. (mm)
Evaporator coil access side . . . . . . . . . . . . . . . . . . 36 (914)
Power entry side (except for NEC requirements) . . . . . . . . . 36 (914)
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)
Side opposite ducts
. . . . . . . . . . . . . . . . . . . . . 36 (914)
Duct panel . . . . . . . . . . . . . . . . . . . . . . . . 12 (304.8)*
*Minimum distances: If unit is placed less than 12 in. (304.8 mm) from wall
system, then the system performance may be compromised.
REQ'D CLEARANCES TO COMBUSTIBLE MAT'L. in. (mm)
Top of unit . . . . . . . . . . . . . . . . . . . . . . . . . 14 (355.6)
Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . 2 (50.8)
Side opposite ducts . . . . . . . . . . . . . . . . . . . . . 14 (355.6)
Bottom of unit . . . . . . . . . . . . . . . . . . . . . . . 0.50 (12.7)
Flue panel . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914.4)
NEC REQ'D CLEARANCES. in. (mm)
Between units, power entry side
. . . . . . . . . . . . . . 42 (1066.8)
Unit and ungrounded surfaces, power entry side . . . . . . . . . 36 (914)
Unit and block or concrete walls and other grounded
surfaces, control box side
. . . . . . . . . . . . . . . . . 42 (1066.8)
LEGEND
CG
–
Center of Gravity
COND
–
Condenser
EVAP
–
Evaporator
NEC
–
National Electrical Code
REQ'D –
Required
NOTE: Dimensions are in mm [in.]
UNIT
582A
ELECTRICAL
CHARACTERISTICS
UNIT WEIGHT
CENTER OF GRAVITY
in. [mm]
lb
kg
X
Y
Z
048090/115/130
208-230/1/60, 208/230-3-60, 460-3-60
415
188.6
22 [558.5]
16 [406.4]
17 [432.0]
060090/115/130
208/230-1-60, 208/230-3-60, 460-3-60
450
204.5
22 [558.5]
16 [406.4]
17 [432.0]
8