Guide specifications

GENERAL

System Description

Outdoor-mounted, air-cooled, split-system air conditioner

unit suitable for ground or rooftop installation. Unit consists
of a hermetic compressor, an air-cooled coil, propeller-type
condenser fan, and a control box. Unit will discharge supply
air upward as shown on contract drawings. Unit will be used
in a refrigeration circuit to match up to a packaged fan coil
or coil unit.

Quality Assurance

Unit will be rated in accordance with the latest edition of

ARI Standard 210.

Unit will be certified for capacity and efficiency, and listed

in the latest ARI directory.

Unit construction will comply with latest edition of ANSI/

ASHRAE and with NEC.

Unit will be constructed in accordance with UL standards

and will carry the UL label of approval. Unit will have c-UL
approval.

Unit cabinet will be capable of withstanding Federal Test

Method Standard No. 141 (Method 6061) 500-hr salt spray
test.

Air-cooled condenser coils will be leak tested at 250 psig

and pressure tested at 450 psig.

Unit constructed in ISO9001 approved facility.

Delivery, Storage, and Handling

Unit will be shipped as single package only and is stored

and handled per unit manufacturer’s recommendations.

Warranty (for inclusion by specifying engineer)

U.S. and Canada only.

PRODUCTS

Equipment

Factory assembled, single piece, air-cooled air conditioner

unit. Contained within the unit enclosure is all factory
wiring, piping, controls, compressor, refrigerant charge
Puron®, and special features required prior to field start-up.

Refrigerant

Refrigerant will be Puron HFC refrigerant with zero ozone

depletion potential. Puron is approved under the EPA’s
Significant New Alternatives Policy (SNAP) Program.

Unit Cabinet

Unit cabinet will be constructed of galvanized steel,

bonderized, and coated with a powder coat paint.

Fans

Condenser fan will be direct-drive propeller type,

discharging air upward.

Air-Cooled, Split-System

Air Conditioner

598B

2 to 5 Tons Nominal

Condenser fan motors will be totally enclosed, 1-phase

type with class B insulation and permanently lubricated
bearings.

Shafts will be corrosion resistant.
Fan blades will be statically and dynamically balanced.
Condenser fan openings will be equipped with PVC-coated

steel wire safety guards.

Compressor

Compressor will be hermetically sealed.
Compressor will be mounted on rubber vibration isolators.

Condenser Coil

Condenser coil will be air cooled.
Coil will be constructed of aluminum fins mechanically

bonded to copper tubes which are then cleaned, dehydrated,
and sealed.

Refrigeration Components

Refrigeration circuit components will include liquid-line

shutoff valve with sweat connections, vapor-line shutoff
valve with sweat connections, system charge of refrigerant
Puron® (R-410A), and compressor oil.

Unit will be equipped with factory supplied TXV

(Thermostatic Expansion Valve), high pressure switch, low
pressure switch, and filter drier for Puron refrigerant.

Operating Characteristics

The capacity of the unit will meet or exceed _____ Btuh at

a suction temperature of _____ °F. The power consumption
at full load will not exceed _____ kW.

Combination of the unit and the evaporator or fan coil unit

will have a total net cooling capacity of _____ Btuh or
greater at conditions of _____ CFM entering air temperature
at the evaporator at _____ °F wet bulb and _____ °F dry
bulb, and air entering the unit at _____ °F.

The system will have an SEER of _____ Btuh/watt or

greater at DOE conditions.

Electrical Requirements

Nominal unit electrical characteristics will be _____ v,

single phase, 60 Hz. The unit will be capable of satisfactory
operation within voltage limits of _____ v
to _____ v.

Unit electrical power will be single point connection.
Control circuit will be 24v.

Special Features

Refer to section of this literature identifying accessories

and descriptions for specific features and available
enhancements.