beautypg.com

Bryant 187B User Manual

Page 11

background image

11

OAT Thermistor must be

locked in place with spherical

nib end facing towards the

front of the control box

Fig. 8 -- Outdoor Air Thermistor (OAT) Attachment

OCT Thermistor must be

secured tight on the liquid tube.

Fig. 9 -- Outdoor Coil Thermistor (OCT) Attachment

Table 6 – TROUBLESHOOTING

OPERATION

FAULT

AMBER

LED

FLASH

CODE

POSSIBLE CAUSE AND ACTION

Standby – no call for unit op-

eration

None

On sol-

id, no

flash

Normal operation

Low---stage Cool/Heat Opera-

tion

None

1, pause

Normal operation

High-stage Cool/Heat Opera-

tion

None

2, pause

Normal operation

System Communications

Failure

16

Communication with user interface lost. Check wiring to User Interface, indoor

and outdoor units

Invalid Model Plug

25

Control does not detect a model plug or detects an invalid model plug. Unit

will not operate without correct model plug.

High Pressure Switch Open

31*

High---pressure switch trip. Check refrigerant charge, outdoor fan operation

and coils for airflow restrictions.

Low Pressure Switch Open

32*

Low pressure switch trip. Check refrigerant charge and indoor air flow

Control Fault

45

Outdoor unit control board has failed. Control board needs to be replaced.

Brown Out (230 v)

46

Line voltage < 187v for at least 4 seconds. Compressor and fan operation not

allowed until voltage>190v. Verify line voltage.

No 230v at Unit

47

There is no 230v at the contactor when indoor unit is powered and cooling/

heating demand exists. Verify the disconnect is closed and 230v wiring is

connected to the unit.

Outdoor Air Temp Sensor

Fault

53

Outdoor air sensor not reading or out of range. Ohm out sensor and check

wiring.

Outdoor Coil Sensor Fault

55

Coil sensor not reading or out of range. Ohm out sensor and check wiring.

Thermistors out of range

56

Improper relationship between coil sensor and outdoor air sensor. Ohm out

sensors and check wiring.

Low stage Thermal Cutout

71*

Compressor operation detected then disappears while low---stage demand

exists. Possible causes are internal compressor overload trip or start relay and

capacitor held in circuit too long(if installed)

High stage Thermal Cutout

72*

Compressor operation detected then disappears while high---stage demand

exists. Possible causes are internal compressor overload trip or start relay and

capacitor held in circuit too long (if installed)

Contactor Shorted

73

Compressor voltage sensed when no demand for compressor operation

exists. Contactor may be stuck closed or there is a wiring error.

No 230V at Compressor

74

Compressor voltage not sensed when compressor should be starting. Contac-

tor may be stuck open or there is a wiring error.

Low-stage Thermal Lockout

81

Thermal cutout occurs in three consecutive low/ high---stage cycles.

low---stage locked out for 4 hours or until 24v power recycled.

High-stage Thermal Lock-

out

82

Thermal cutout occurs in three consecutive high/low---stage cycles.

high---stage locked out for 4 hours or until 24v power recycled.

Low Pressure Lockout

83

Low pressure switch trip has occurred during 3 consecutive cycles. Unit oper-

ation locked out for 4 hours or until 24v power recycled.

High Pressure Lockout

84

High pressure switch trip has occurred during 3 consecutive cycles. Unit oper-

ation locked out for 4 hours or until 24v power recycled.

* Sequence: Compressor contactor is de-energized and outdoor fan is energized for up to 15 minutes. If demand still exists, control will energize compressor.

187B

/180B