23— condenser only ratings* continued – Bryant Electric 594D User Manual

Page 23

background image

—23—

CONDENSER ONLY RATINGS* Continued

* ARI listing applies only to systems shown in Performance Data table.

KW

— Total Power (kW)

SDT

— Saturated Temperature Leaving Compressor (°F)

SST

— Saturated Temperature Entering Compressor (°F)

TCG

— Gross Cooling Capacity (1000 Btuh)

SST

°F

CONDENSER ENTERING AIR TEMPERATURES °F

55

65

75

85

95

105

115

594D042-E, F

30

TCG

39.4

37.6

35.7

33.9

32.0

30.2

28.4

SDT

77.0

86.9

96.8

107.0

117.0

127.0

137.0

KW 2.17

2.43

2.72

3.04

3.40

3.81

4.26

35

TCG

43.3

41.4

39.4

37.4

35.4

33.4

31.4

SDT

78.5

88.2

98.0

108.0

118.0

128.0

138.0

KW 2.19

2.45

2.74

3.07

3.43

3.84

4.30

40

TCG

47.5

45.4

43.3

41.1

39.0

36.8

34.6

SDT

80.0

89.7

99.5

109.0

119.0

129.0

139.0

KW 2.21

2.48

2.77

3.10

3.47

3.88

4.34

45

TCG

51.8

49.6

47.4

45.1

42.7

40.4

38.1

SDT

81.7

91.4

101.0

111.0

121.0

131.0

141.0

KW 2.24

2.51

2.80

3.14

3.51

3.92

4.39

50

TCG

56.4

54.1

51.7

49.2

46.7

44.2

41.7

SDT

83.6

93.2

103.0

113.0

122.0

132.0

142.0

KW 2.27

2.54

2.84

3.18

3.55

3.97

4.44

55

TCG

61.2

58.8

56.2

53.6

51.0

48.3

45.6

SDT

85.6

95.1

105.0

114.0

124.0

134.0

144.0

KW 2.31

2.58

2.88

3.22

3.60

4.03

4.50

594D048-E, G

30

TCG

46.0

43.8

41.6

39.3

36.9

34.4

32.0

SDT

80.1

89.8

99.6

109.0

119.0

129.0

139.0

KW 2.46

2.82

3.22

3.65

4.13

4.64

5.17

35

TCG

50.4

48.1

45.7

43.2

40.7

38.1

35.5

SDT

81.9

91.6

101.0

111.0

121.0

131.0

140.0

KW 2.49

2.85

3.25

3.69

4.18

4.71

5.25

40

TCG

55.1

52.6

50.1

47.4

44.7

41.9

39.1

SDT

83.9

93.4

103.0

113.0

123.0

132.0

142.0

KW 2.52

2.88

3.29

3.74

4.23

4.77

5.34

45

TCG

60.0

57.4

54.7

51.9

49.0

46.0

43.0

SDT

86.0

95.5

105.0

115.0

124.0

134.0

144.0

KW 2.55

2.92

3.33

3.79

4.29

4.84

5.43

50

TCG

65.2

62.4

59.6

56.6

53.5

50.3

47.1

SDT

88.3

97.7

107.0

117.0

126.0

136.0

146.0

KW 2.59

2.96

3.38

3.84

4.35

4.91

5.51

55

TCG

70.7

67.7

64.6

61.5

58.2

54.8

51.3

SDT

90.7

100.0

109.0

119.0

128.0

138.0

148.0

KW 2.64

3.01

3.43

3.90

4.42

4.98

5.60

594D060-E, F

30

TCG

55.1

52.7

50.1

47.4

44.8

42.2

39.5

SDT

80.2

89.9

99.7

109.0

119.0

129.0

139.0

KW 3.06

3.44

3.86

4.34

4.87

5.46

6.07

35

TCG

60.3

57.7

55.0

52.1

49.2

46.4

43.5

SDT

82.1

91.8

101.0

111.0

121.0

131.0

141.0

KW 3.10

3.49

3.92

4.40

4.93

5.53

6.17

40

TCG

65.7

63.0

60.1

57.1

54.0

50.9

47.8

SDT

84.1

93.7

103.0

113.0

123.0

133.0

143.0

KW 3.16

3.55

3.99

4.47

5.01

5.61

6.27

45

TCG

71.4

68.6

65.6

62.3

59.0

55.6

52.3

SDT

86.3

95.9

105.0

115.0

125.0

135.0

144.0

KW 3.21

3.62

4.06

4.55

5.09

5.69

6.36

50

TCG

77.4

74.5

71.3

67.8

64.3

60.6

57.0

SDT

88.6

98.1

108.0

117.0

127.0

136.0

146.0

KW 3.28

3.69

4.14

4.64

5.19

5.79

6.46

55

TCG

83.8

80.7

77.3

73.7

69.9

66.0

62.0

SDT

91.1

101.0

110.0

120.0

129.0

139.0

148.0

KW 3.35

3.77

4.23

4.74

5.29

5.90

6.58

SYSTEM DESIGN SUMMARY

1.

Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01 in. wc.

2.

Minimum outdoor operating air temperature without low-ambient operation accessory is 55°F (12.8°C).

3.

Maximum outdoor operating air temperature is 125°F (51.7°C).

4.

For reliable operation, unit should be level in all horizontal planes.

5.

Maximum elevation of indoor coil above or below base of outdoor unit is: Indoor coil above = 50 ft. Indoor coil below = 150 ft.

6.

For interconnecting refrigerant tube lengths greater than 50 ft or 20 ft vertical differential, consult Residential Split System Long-Line Application
Guidelines available from equipment distributor.

7.

Crankcase heater required when interconnecting refrigerant tube length exceeds 50 ft.

8.

Not more than 3 ft of refrigerant tube should be buried in the ground. If necessary to bury tubes under a sidewalk, provide a minimum 6-in. vertical
rise to the valve connections at the unit. For buried lines longer than 3 ft, consult your local distributor.

9.

Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided

10. Mismatches of indoor coil capacity more than 1 size larger than outdoor unit capacity may result in inadequate indoor comfort.
11. Do not apply capillary tube indoor coils to these units.