Convenience

Outlet

GFCI

Pwd-CO

Fuse

Switch

Pwd-CO

Transformer

Control Box

Access Panel

C08128

Fig. 17 -- Convenience Outlet Location

Installing Weatherproof Cover –

A

weatherproof

while-in-use

cover

for

the

factory-installed convenience outlets is now required by

UL standards. This cover cannot be factory-mounted due

its depth; it must be installed at unit installation. For

shipment, the convenience outlet is covered with a blank

cover plate.

The weatherproof cover kit is shipped in the unit’s control

box. The kit includes the hinged cover, a backing plate

and gasket.

DISCONNECT

ALL

POWER

TO

UNIT

AND

CONVENIENCE OUTLET.

Remove the blank cover plate at the convenience outlet;

discard the blank cover.

Loosen the two screws at the GFCI duplex outlet, until

approximately

1

/

2

-in (13 mm) under screw heads are

exposed. Press the gasket over the screw heads. Slip the

backing plate over the screw heads at the keyhole slots

and align with the gasket; tighten the two screws until

snug (do not over-tighten).

Mount the weatherproof cover to the backing plate as

shown in Fig. 18. Remove two slot fillers in the bottom of

the cover to permit service tool cords to exit the cover.

Check for full closing and latching.

RECEPTACLE
NOT INCLUDED

COVER – WHILE-IN-USE
WEATHERPROOF

BASE PLATE FOR
GFCI RECEPTACLE

C09022

Fig. 18 -- Weatherproof Cover Installation

Non--powered type: This type requires the field

installation of a general--purpose 125--volt 15--A circuit

powered from a source elsewhere in the building. Observe

national and local codes when selecting wire size, fuse or

breaker requirements and disconnect switch size and

location. Route 125--v power supply conductors into the

bottom of the utility box containing the duplex receptacle.

Unit--powered type: A unit--mounted transformer is

factory--installed to stepdown the main power supply

voltage to the unit to 115--v at the duplex receptacle. This

option also includes a manual switch with fuse, located in

a utility box and mounted on a bracket behind the

convenience outlet; access is through the unit’s control

box access panel. See Fig. 17.

The primary leads to the convenience outlet transformer

are not factory--connected. Selection of primary power

source is a customer--option. If local codes permit, the

transformer primary leads can be connected at the

line--side terminals on the unit--mounted non--fused

disconnect or HACR breaker switch; this will provide

service power to the unit when the unit disconnect switch

or HACR switch is open. Other connection methods will

result in the convenience outlet circuit being de--energized

when the unit disconnect or HACR switch is open. See

Fig. 19.

C08283

UNIT

VOLTAGE

CONNECT

AS

PRIMARY

CONNECTIONS

TRANSFORMER

TERMINALS

208,

230

240

L1: RED +YEL

L2: BLU + GRA

H1 + H3

H2 + H4

460

480

L1: RED

Splice BLU + YEL

L2: GRA

H1

H2 + H3

H4

575

600

L1: RED

L2: GRA

H1

H2

Fig. 19 -- Powered Convenience Outlet Wiring

Fuse on power type: The factory fuse is a Bussman

“Fusetron” T--15, non--renewable screw--in (Edison base)

type plug fuse.

551J