Environmental requirements, Power cords (japan, denan) – Brocade Communications Systems Extension Switch 7800 User Manual
Page 43

Brocade 7800 Extension Switch Hardware Reference Manual
31
53-1001350-04
Environmental requirements
A
lists the power supply specifications for the Brocade 7800.
Environmental requirements
lists the acceptable environmental ranges for both operating and nonoperating (such as
during transportation or storage) conditions
Power cords (Japan, Denan)
TABLE 8
Power supply specifications
Specification
Value
Maximum output of one power supply
150 watts
System DC power consumption (excluding
power supply and fan FRUs)
Idle: 95 W
Maximum: 116 W
Input system power (including power supply
and fan FRUs)
Idle: 145 W
Maximum: 173 W
Input voltage
85-264 VAC
Input line frequency
47-63 Hz
BTU rating
590 BTU/hr
Inrush current
Maximum of 60A for period of 10-150mS
Input line protection
Both AC lines are fused
TABLE 9
Environmental requirements
Condition
Acceptable during operation
Acceptable during non-operation
Ambient Temperature
0º to 40º C
32º to 104º F
-25º to 70º C
-13º to 158º F
Humidity
10% to 85% RH non-condensing, at
40º C (104º F)
10% to 90% RH non-condensing, at
70º C (158º F)
Altitude
0 to 3 km (9,842 feet) above sea level
0 to 12 km (39,370 feet) above sea
level
Shock
20 G, 6 ms, half-sine wave
15 G, 12-18 ms, trapezoid
Vibration
0.5 G sine, 5-500 Hz
2.0 G sine, 5-500 Hz
Air flow
Maximum - 101.94 cmh (60 cfm)
Nominal - 74.76 cmh (44 cfm)
NA