SECTION II

MASONRY INSERT INSTALLATION

The Model 81 may be installed using an all masonry fireplace built in accordance with the
Uniform Building Code and National Fire Protection Association (NFPA). The first step in
this type of installation is to determine acceptability of fireplace and chimney for use with a
woodstove. Both construction and condition of fireplace are important consid-
erations when installing a woodstove. The chimney should extend at least 3' above roof and
at least 2' above any point of roof within 10'.

CAUTION

REMEMBER TO HAVE YOUR CHIMNEY INSPECTED FOR LEAKS AND BLOCKAGE
BEFORE YOU INSTALL YOUR STOVE. “DO NOT CONNECT THIS UNIT TO A
CHIMNEY FLUE SERVING ANOTHER APPLIANCE.”

MINIMUM CLEARANCE MASONRY INSERT



A. Side Wall Combustible
B. Front Floor Protector
C. Side Floor Protector
D. Side Wood Trim
E. Top Wood Trim
F. Mantel or Brackets



12"
16"
8"
7"
10"
21"

MODEL 81

1. The hearth must be of masonry construction and must extend a minimum of 16" in front of

firebox opening and a minimum of 8" to either side of firebox opening.

2. If there is not minimum hearth protection from front of firebox opening and front of
masonry hearth, a floor protector must be used in front of hearth to protect combustible
materials. The floor protector must be 3/8" minimum thickness non-combustible material
or equivalent.(See Page 6).

F

B

A

E

C

D

Page 5