Replacing Pilot and Control Valve Series GWU501E, GWU511A, GWU512A LP Gas 606030

20

For assistance call 1.800.762.1142.

Tank/Gas Line Connection

1. Make 2-3 oz. of leak solution by mixing one part liquid dishwashing soap with three parts water.

2. Make sure control knobs are off.

3. Turn LP gas tank ON at valve.

4. Spoon leak check solution at all “x” locations

5. If any bubbles appear turn LP gas tank OFF, reconnect and re-test. If you continue to see bubbles after

several attempts, disconnect LP gas source and contact 1.800.762.1142 for assistance.

6. If no bubbles appear after one minute turn tank OFF, wipe away solution and proceed.

Pilot, Pilot Supply Tube, Control Valve and Burner Supply Tube

1. Make 2-3 oz. of leak solution by mixing one part liquid dishwashing soap with three parts water.

2. Turn LP gas tank ON at valve.

3. Turn control knob on to LOW

4. Remove access panel

5. Place leak solution on pilot supply tube at the pilot and at the control valve.

6. Place leak solution on the burner supply tube.

7. If any bubbles appear turn control valve OFF, check all connection to make sure they are tight, and retest. If

you continue to see bubbles after several attempts, turn control valve off and disconnect LP gas source and
contact 1.800.762.1142 for assistance.

8. If no bubbles appear after one minute turn tank OFF, wipe away solution and proceed.

X

X

X

X

X