Replacing battery (continued) – Belkin F6C700-EUR User Manual
Page 22
18
5. Disconnect the battery:
•
For F6C700
-EUR
(700VA) and F6C1000
-EUR
(1000VA) models,
disconnect the batteries and UPS by loosening the connectors.
•
For F6C1400
-EUR
(1400VA) model, disconnect the batteries
and UPS by pulling apart the two white couplers that are
connected together.
6. Connect the new battery:
•
For 700VA and 1000VA models, connect positive (+) connectors
(RED-RED) and negative (-) connectors (BLACK-BLACK) together.
•
For 1400VA model, connect the two white connected couplers on
battery and UPS together.
7. Re-assemble the UPS as shown above.
8. For environmental protection, do not dispose old batteries anywhere.
Contact your battery supplier for proper recycling of old batteries.
Replacing Battery (continued)
Black (-)
Black (-)
Black (-)
1400VA
1000VA
Red (+)
Red (+)
Red (+)
Push back to UPS
Push back to UPS
Push back to UPS
700VA