6. Refer to Table 4. Find outdoor temperature and evaporator

entering air wet-bulb temperature. At this intersection, note
superheat.

7. Refer to Table 5. Find superheat temperature located in item

6 and suction pressure. At this intersection, note suction line
temperature.

8. If unit has a higher suction line temperature than charted

temperature, add refrigerant until charted temperature is
reached.

9. If unit has a lower suction line temperature than charted

temperature, reclaim refrigerant until charted temperature is
reached.

10. When adding refrigerant, charge in liquid form into suction

service port using a flow-restricting device.

11. If outdoor air temperature or pressure at suction valve

changes, charge to new suction line temperature indicated
on chart.

XIII.

FINAL CHECKS

IMPORTANT:

Before leaving job, be sure to do the following:

1. Ensure that all wiring is routed away from tubing and sheet

metal edges to prevent rub-through or wire pinching.

2. Ensure that all wiring and tubing is secure in unit before

adding panels and covers. Securely fasten all panels and
covers.

3. Tighten service valve stem caps to 1/12-turn past finger

tight.

4. Leave User’s Manual with owner. Explain system operation

and periodic maintenance requirements outlined in manual.

5. Fill out Dealer Installation Checklist and place in customer

file.

CARE AND MAINTENANCE

For continuing high performance and to minimize possible equip-
ment failure, periodic maintenance must be performed on this
equipment.

Frequency of maintenance may vary depending upon geographic
areas, such as coastal applications. See Users Manual for informa-
tion.

TABLE 4—SUPERHEAT CHARGING

OUTDOOR TEMP (°F)

EVAPORATOR ENTERING AIR TEMPERATURE (°F WB)

50

52

54

56

58

60

62

64

66

68

70

72

74

76

55

9

12

14

17

20

23

26

29

32

35

37

40

42

45

60

7

10

12

15

18

21

24

27

30

33

35

38

40

43

65

6

10

13

16

19

21

24

27

30

33

36

38

41

70

7

10

13

16

19

21

24

27

30

33

36

39

75

6

9

12

15

18

21

24

28

31

34

37

80

5

8

12

15

18

21

25

28

31

35

85

8

11

15

19

22

26

30

33

90

5

9

13

16

20

24

27

31

95

6

10

14

18

22

25

29

100

8

12

15

20

23

27

105

5

9

13

17

22

26

110

6

11

15

20

25

115

8

14

18

23

Where a dash (—) appears, do not attempt to charge system under these conditions or refrigerant slugging may occur. Charge must be weighed in.
NOTE: Superheat °F is at low-side service port.

TABLE 5—REQUIRED SUCTION-LINE TEMPERATURE

SUPERHEAT

TEMP

(°F)

SUCTION PRESSURE AT SERVICE PORT (PSIG)

107.8

112.2

116.8

121.2

126.0

130.8

138.8

140.8

145.8

0

35

37

39

41

43

45

47

49

51

2

37

39

41

43

45

47

49

51

53

4

39

41

43

45

47

49

51

53

55

6

41

43

45

47

49

51

53

55

57

8

43

45

47

49

51

53

55

57

59

10

45

47

49

51

53

55

57

59

61

12

47

49

51

53

55

57

59

61

63

14

49

51

53

55

57

59

61

63

65

16

51

53

55

57

59

61

63

65

67

18

53

55

57

59

61

63

65

67

69

20

55

57

59

61

63

65

67

69

71

22

57

59

61

63

65

67

69

71

73

24

59

61

63

65

67

69

71

73

75

26

61

63

65

67

69

71

73

75

77

28

63

65

67

69

71

73

75

77

79

30

65

67

69

71

73

75

77

79

81

32

67

69

71

73

75

77

79

81

83

34

69

71

73

75

77

79

81

83

85

36

71

73

75

77

79

81

83

85

87

38

73

75

77

79

81

83

85

87

89

40

75

77

79

81

83

85

87

89

91

—8—