beautypg.com

Bryant 591B User Manual

Page 4

background image

CAUTION:

To prevent improper performance and/or

unit component failures, do not leave system open to
atmosphere any longer than minimum required for instal-
lation. POE oil in compressor is extremely susceptible to
moisture absorption. Always keep ends of tubing sealed
during installation.

CAUTION:

To prevent improper performance or equip-

ment failure this caution must be followed. If ANY
refrigerant tubing is buried, provide a 6 in. vertical rise at
service valve. Refrigerant tubing lengths up to 36 in. may
be buried without further special consideration. Do not
bury lines over 36 in. in length.

CAUTION:

To prevent damage to unit or service valves

observe the following:
• Use a brazing shield.
• Wrap service valves with wet cloth or use a heat sink
material.

Outdoor units may be connected to indoor section using accessory
tubing package or field-supplied refrigerant grade tubing of correct
size and condition. For tubing requirements beyond 50 ft, substan-
tial capacity and performance losses can occur. Following the
recommendations in the Application Guideline and Service

Manual—Air Conditioners and Heat Pumps Using Puron® Refrig-
erant will reduce these losses. Refer to Table 1 for field tubing
diameters. Refer to Table 2 for accessory requirements.

There are no buried-line applications greater than 36 in.

If refrigerant tubes or indoor coil are exposed to atmosphere, they
must be evacuated to 500 microns to eliminate contamination and
moisture in the system.

A.

OUTDOOR

UNIT

CONNECTED

TO

FACTORY-

APPROVED INDOOR UNIT

Factory refrigerant charge is for a 15 ft line set. Outdoor unit
contains correct system refrigerant charge for operation with ARI
rated indoor unit. Check refrigerant charge for maximum effi-
ciency. The charge must be adjusted based on the actual line set
length. Add or subtract 0.6 oz/ft for line sets longer or shorter than
15 ft.

B.

INSTALL LIQUID-LINE FILTER DRIER

CAUTION:

To avoid performance loss and compressor

failure, installation of filter drier in liquid line is required.

Refer to Fig. 6 and install filter drier as follows:

1. Braze 5-in. connector tube to liquid service valve. Wrap

filter drier with damp cloth.

2. Braze filter drier between connector tube and liquid tube to

indoor coil. Flow arrow must point towards indoor coil.

TABLE 1—REFRIGERANT CONNECTIONS AND RECOMMENDED LIQUID AND VAPOR TUBE DIAMETERS (IN.)

UNIT SIZE

LIQUID

VAPOR

VAPOR (LONG LINE)

Connection Diameter

Tube Diameter

Connection Diameter

Tube Diameter

Connection Diameter

Tube Diameter

018, 024

3/8

3/8

5/8

5/8

5/8

3/4

030, 036

3/8

3/8

3/4

3/4

3/4

7/8

042, 048

3/8

3/8

7/8

7/8

7/8

1-1/8

060

3/8

3/8

7/8

1-1/8

7/8

1-1/8

NOTES:
1. Tube diameters are for lengths up to 50 ft. For tubing lengths greater than 50 ft, consult the Application Guideline and Service Manual—Air Conditioners and Heat Pumps

Using Puron®.

2. Do not apply capillary tube indoor coils to these units.

TABLE 2—ACCESSORY USAGE

ACCESSORY

REQUIRED FOR

LOW-AMBIENT

APPLICATIONS

(BELOW 55°F)

REQUIRED FOR

LONG-LINE

APPLICATIONS*

(OVER 50 FT)

REQUIRED FOR

SEA COAST

APPLICATIONS

(WITHIN 2 MILES)

Crankcase Heater

Yes

Yes

No

Evaporator Freeze Thermostat

Yes

No

No

Winter Start Control

Yes†

No

No

Accumulator

No

No

No

Compressor Start Assist

Capacitor and Relay

Yes

Yes

No

MotorMaster® Control,

or

Low-Ambient Pressure Switch

Yes

No

No

Wind Baffle

See Low-Ambient Instructions

No

No

Coastal Filter

No

No

Yes

Support Feet

Recommended

No

Recommended

Liquid-Line Solenoid Valve

or

Hard Shutoff TXV

No

See Long-Line Application Guideline

No

Ball Bearing Fan Motor

Yes‡

No

No

* For Tubing Sets between 50 and 175 ft horizontal or 20 ft vertical differential, refer to the Application Guideline and Service Manual—Air Conditioners and Heat Pumps

Using Puron®.

† Only when low-pressure switch is used.
‡ Required for low-ambient controller (full modulation feature) and MotorMaster® Control only.

—4—