ADT-LCD40 Series Electrical Connections

Wiring FACP to ADT-LCD40 Series

24

Document 50520 Rev D 7/25/00 P/N 50520:D

Dim-485 Installation.

CAUTION! Connect all wiring to the DIM-485 terminals before
plugging it into connector J11 on the Unimode 200 circuit board.

1. Carefully align the DIM-485 connector with the four pins on

connector J11 of the Unimode 200

2. Press firmly on the DIM-485 connector to seat properly on

connector J11 being careful not to bend any pins

3. Be certain to secure the DIM-485 module to the Unimode 200

and keep all wiring from mechanically interfering with module.

Figure 4-4: Wiring FACP to ADT-LCD40 Series

1 2 3 4

P1

P2

1 2 3 4

1 2 3 4 5 6 7

Ferrite Core P/N FBD-1

Required

Ferrite Core P/N FBD-1

Required

ADT-LCD40 Series in

grounded box

ADT-LCD40 Series in

grounded box

EIA-485

24 VDC

TB4 Terms

3(+) & 4(-)

DIM-485

Unimode 200

in grounded box

Top

(+) EIA-485

IN

(-) EIA-485

(+) (-)

EIA-485

OUT

(+) 24 VDC

IN

(-) 24 VDC

n/c

Earth

Ground

Optional

Shield

Connect

(+) (-)

24 VDC

OUT

Notes:

1) Ferrite Core P/N FBD-1 is required to meet

FCC Part 15 requirements if the EIA-485

wiring is not in conduit. Twisted, shielded

wire is recommended for the EIA-485

communications loop.

2) Six conductor overall shielded wire may be

used for the four EIA-485 wires and the two

power wires. It is, however, strongly

recommended that the power and communi-

cation wires be separate whenever possible.