SURT192RMXLBP2/SURT192XLBP2 6U User Manual
Operation
Battery LED
The battery LED is located on the front bezel of the XLBP. During normal operation the LED is not
illuminated.
On start-up the XLBP LED may illuminate and blink within the first minute. The LED should then extinquish.
LED Activity
Possible Cause
XLBP LED illuminates briefly
~ On start-up the XLBP LED may illuminate
and blink within the first minute.
~ The
XLBP
is establishing communication
with other components of the system.
~ The XLBP is conducting a normal periodic
self test
Normal operation
XLBP LED remains illuminated after start-up or illuminates during operation
XLBP LED is blinking slowly
(one blink per second).
One or more battery modules are not connected
XLBP LED is blinking rapidly
(three blinks per second).
A communication fault exists, check cable connections
The XLBP LED remains illuminated.
~ A potential hardware fault exists contact APC, refer to the Service
section in this manual
Battery module and pair identification
The PowerView will reference XLBP configuration in the
following manner.
External Battery Pack
BattPair_1
BattPair_2
Module_1
Module_2
Module_3
Module_4
BattPair_3
BattPair_4
Module_5
Module_6
Module_7
Module_8