8

Status

n Status Display 1

Ÿ Input Line Voltage and Frequency

Ÿ Output Voltage

Ÿ Runtime Estimate

Ÿ Load (in Amps and % of VA capacity)

n Status Display 2

Ÿ UPS internal temperature

Ÿ Last Transfer: the cause of the most recent on-battery event.

None -

the UPS has not been on battery recently.

Test -

a self-test caused the UPS to briefly run on
battery.

Notch/Spike - AC line voltage was non-sinusoidal or se-

verely distorted; includes total power failure.

Low Voltage -

AC line voltage went below the lower transfer
point. The lower transfer point is user adjust-
able in certain UPS models, see
Setup:Transfer

menu.

Hi Voltage -

AC line voltage exceeded the upper transfer
point. The upper transfer point is user adjust-
able in certain UPS models, see
Setup:Transfer

menu.

Rate of Chng - abrupt change in line voltage
CirBrkr Trip - input circuit breaker tripped (Symmetra

only)

Ÿ Status: a terse indication of the state of the UPS. The most

common are On-Line (AC line quality is acceptable), UPS/
Load off, On-battery (load is powered from battery), Low-
Battery (battery is fully discharged), Overload, or any one of
a number of internal faults. Use Diagnostics from the top
level menu for a detail of the UPS status and faults.

Ÿ Number of installed batteries and bad batteries (Matrix-UPS

and Symmetra only)