Smoke alarm, Tandem wiring diagram relay models, Isolated thermal with optional accessory contacts – Silent Call Gentex 7100F User Manual
Page 3
![background image](/manuals/468054/3/background.png)
120 VOLTS
60 HZ
RED / YEL
WHT
BLK
SMOKE
ALARM
ACCESS
CONTACTS
ALARM
CONTACTS
TANDEM
POWER
CAUTION:
RED/YELLOW wire to be capped
when not in use. This wire is for
tandem connection only. Do not
connect to any other circuit.
7000/7003 Series Wiring Diagrams
ELECTRICAL
BOX
QUICK
DISCONNECT
TYPE PLUG
SMOKE
ALARM
1
2
3
T
ANDEM WIRE
NEUT
HOT
TO ADDITIONAL
SMOKE OR HEAT
ALARMS
(MAX 12 ALARMS
PER SYSTEM)
Tandem Wiring Diagram
Relay Models
YEL
ORN
BLU
VIO
VIO/BLK
RED/YEL
BLK
WHT
RELAY CONTACTS
RATED LOAD RESISTIVE
1.0 AMP @ 24 VDC
0.6 AMP @ 125 VAC MAX
0.3 AMP @ 220 VAC MAX
Isolated thermal with optional
accessory contacts.
HF ONL
Y
SMOKE
ALARM
HEAT
SENSOR
ACCESS
CONTACTS
ALARM
CONTACTS
TANDEM
POWER
SMOKE
ALARM
SMOKE
ALARM
1
2
3
1
2
3
ELECTRICAL
BOX
ELECTRICAL
BOX
LIMITATIONS:
A Maximum of 12 alarms
(7100/7103, 7100/7103T,
7100/7103H, 7200/7203,
7200/7203T, 7200/7203H)
may be connected together.
Do not exceed 125 feet
between each detector. Do
not exceed 1125 feet
between the first and last
detector. NOTE: Gentex
smoke alarms can not be
interconnected to detectors
from other manufacturers.
A MAXIMUM OF SIX (6)
ALARMS WITH A RELAY
MAY BE TANDEM INTER-
CONNECTED. (7100/7103F,
7100/7103TF, 7100/7103HF,
7200/7203F, 7200/7203TF,
7200/7203HF)
Models
7100/7103F
7100/7103TF
7203/7203F
7200/7203TF