SECTION 7: MAINTENANCE

7.1 General Maintenance

WARNING!

Disconnect the cooling unit from the power

supply before any cleaning or maintenance.

The cooling unit is largely maintenance free.

The cooling circuit is a maintenance free hermetically

sealed system. It has been filled at the factory with

the required refrigerant amount, checked for leakage

and run through a series of functional tests before

being shipped.

The components around the external air circuit require

periodic cleaning and maintenance depending on

the environmental conditions.

7.2 Cleaning

The cleaning intervals depend upon the relevant

operating conditions. In particular, observe the

following instructions:

• Disconnect the cooling unit from the power supply

• Remove the external cover

• Clean the heat exchanger regularly using a soft

brush or pressurized air

• It is recommended that the condensate run off

opening be checked regularly

WARNING!

Damage to the heat exchanger possible.

Do not use any sharp or pointed object to

clean the condenser heat exchanger.

The heat exchanger fins should not be bent,

compressed or damaged in any way during

the cleaning process.

If the cooling units are provided with a filter, clean

the filter mat regularly. The cleaning intervals or the

intervals for replacement of the filter mat mainly

depends upon environmental conditions (air quality.)

You can rinse the filter mat using water heated to

40° C and commercially available mild detergent.

It is possible to remove any dirt by knocking the mat

slightly, vacuum cleaning it or blowing it out.

If the filter mat is oily or greasy, please replace.