beautypg.com

Warning – Pfannenberg DTS 3000 Series User Manual

Page 11

background image

8

6.3 Test Mode / Start-up

The start-up / test mode is activated whenever

the unit has had power removed and re-applied.

While in this mode the cooling unit operates

independently from the ambient conditions when

the door contact is closed.

The cooling unit runs through a start up sequence

that takes approximately 30 seconds to accomplish.

The start-up mode is also activated whenever the

door limit switch is closed.

Modus

Time Curve

Characteristics

Start-up

Mode

t = 0s - < 30s

t = 30s

t = 32s

No function.

Internal fan start up.

External fan and compressor start up.

Flashing sequence of the

status indicator:

"off-dark-light-dark-off".

Fault signal contact is closed.

Self Test

during Start

t > 34s - 64s

Compressor and fans remains in

operation during the period.

Flashing sequence of the status indi-

cator: "off-dark-light-off".

Fault signal contact is open.

Should a fault arise during the test

mode, the unit goes into the fault

mode and the status indicator lights

up according to the fault state (See

Section 8.1)

6.4 Door Contact

For safety reasons and to prevent an increased

output of condensate, a door limit switch should be

connected to the terminals provided on the cooling

unit. (see the wiring diagram on the individual

cooling unit or on the individual information sheet

supplied with the cooling unit.

With the switch in place, when the electrical

panel enclosure door is opened (thereby opening

the switch) all of the cooling unit motors are

immediately turned off. When the electrical panel

enclosure door is closed, the cooling unit start-up

mode begins and is run through which ensures a

restart-up of the cooling unit with a time lag.

6.5 Setting the Operating Parameters

Various electrical panel enclosure temperatures as

well as the limit temperatures can be selected by

means of a DIP switch on individual cooling units.

The location of the DIP switch is on the cooling unit

control board as shown on its circuit diagram.

The coding options are represented on the

circuit diagram.

The circuit diagram and / or display image are to

be found on the inside of the service cover of

the cooling unit or on the individual cooling unit

information sheet.

See the cooling unit information sheet for

additional details.

WARNING!

Changes to the operating parameters

of the cooling units should only be made

by authorized personnel.