6. Commissioning, operation

Connection diagram

Menu selection and initialisation instructions for installation

If no button is pressed within 20 seconds, the instrument returns to the

display mode.

1. Press the Select button for 2 seconds to

open the menu.

2. Select the required ventilator manufac-

turer.

3. Each ventilator manufacturer has its own

specific k value.

Please take the right k value from the

data sheet:

Fläkt Woods (k = 0.3 … 99)

Rosenberg

(k = 37 … 800)

Nicotra

(c = 10 … 1,500)

Comefri

(k = 10 … 2,000)

Ziehl

(k = 10 … 1,500)

Ebm-Papst

(k = 10 … 1,500)

Gebhard

(k = 50 … 4,700)

4. The following units will be shown on the

display:

m³/s, m³/h, cfm, l/s, scfh, lpm, kPa, mbar,

mmWS, inchWS or Pa.