6.3.3 Display information overrange/underrange
Range:
4 ... 20 mA
Displayed range:
3.9 ... 20.1 mA
Usable range:
3.6 ... 21.5 mA
Advance warning of underrange: 3.6 ... < 3.9 mA
Advance warning of overrange:
> 20.1 ... 21.5 mA
Underrange displayed:
< 3.6 mA
Overrange displayed:
> 21.5 mA
With the advance warning, the display blinks (normal display
alternates with horizontal bars).
For values under 3.6 mA, a horizontal bar alternates with the display
“undr”. For values over 21.5 mA, a horizontal bar alternates with the
display “over”.
7. Maintenance and cleaning
7.1 Maintenance
The instrument is maintenance-free.
Repairs must only be carried out by the manufacturer.
7.2 Cleaning
CAUTION!
■
Before cleaning, correctly disconnect the instrument
from the pressure supply, switch it off and disconnect it
from the mains.
■
Clean the instrument with a moist cloth.
■
Electrical connections must not come into contact with
moisture.
■
Wash or clean the dismounted instrument before
returning it, in order to protect persons and the
environment from exposure to residual media.
■
Residual media in dismounted instruments can result in
a risk to persons, the environment and equipment. Take
sufficient precautionary measures.