Operating Instructions Temperature Indicating Controller CF1M

V1.

1

03/200

5

- 15 -

h When the difference between setting value and processing temperature is large when

the temperature falls.

Fluctuation is given at the temperature 20°C (°F) or higher than the setting value.

8. Mounting to the control panel

8.1 Site selection

Mount the controller in a place with:

(1) A minimum of dust, and an absence of corrosive gases.
(2) No mechanical vibrations or shocks.
(3) No exposure to direct sunlight, an ambient temperature of 0 to 50°C (32 to122°F)

that does not change suddenly.

(4) An ambient non-condensing humidity of 35 to 85%RH or less.
(5) The controller away from large capacity electromagnetic switches or cables

through which large current is flowing.

(6) No water, oil or chemicals or where the vapors of these substances can

come into direct contact with the unit.

8.2 External dimension drawing

[Fig. 8.2-1]

Packing B

Mounting frame

Terminal cover

48

24

9.5

101.1

98.5

47

.3

44

.8

47

.5

21

.6

23

.8

29

.9

AT

:

AT

Temperature

Setting value

PID parameter measuring

PID parameter calculated point

Controlling action is performed

with the parameters set by auto-

tuning.

Auto-tuning starting point

Time

1

2

3

3

2

1

Temperature 20 ( ) higher than the setting value

C F

AT bias setting value

4

4