Maintenance, cleaning / 8. faults, Faults – WIKA OLS-C20 User Manual

Page 13

background image

WIKA operating instructions mini limit switch, model LSO.02

13

13334591.02 10/2010 GB/D/F/E

GB

7. Maintenance, cleaning / 8. Faults

7.2 Cleaning

CAUTION!

Before cleaning, correctly disconnect the instrument from the pressure

supply, switch it off and disconnect it from the mains.

Clean the instrument with a moist cloth.

Electrical connections must not come into contact with moisture.

Wash or clean the dismounted instrument before returning it, in order to

protect staff and the environment from exposure to residual media.

Residual media in dismounted instruments can result in a risk to persons,

the environment and equipment. Take sufficient precautionary measures.

For information on returning the instrument see chapter "10.2 Return".

8. Faults

Faults

Possible causes

Measures

No function

No power supply

Measure power supply, check

connection to cable or plug

No function in spite of

liquid level change

Contamination or scale on

the glass-tip

Clean glass-tip (set up periodic

maintenance)

Sensor works to reverse

logic

SA instead of SE or SE

instead of SA specified

Change sensor

CAUTION!

If faults cannot be eliminated by means of the measures listed above, the

instrument must be shut down immediately, and it must be ensured that

pressure and/or signal are no longer present, and it must be prevented from

being inadvertently put back into service.

In this case, contact the manufacturer.

If a return is needed, please follow the instructions given in chapter

"10.2 Return".