Sil declaration of conformity, Appendix 1: sil declaration of conformity – WIKA T32.xS User Manual
Page 16
GB
16
11583631.02 11/2010 GB/D/F/E
WIKA safety manual temperature transmitter T32.xS
SIL Declaration of Conformity
Functional safety per DIN EN 61508 / DIN EN 61511
WIKA Alexander Wiegand SE & Co. KG, Alexander Wiegand Straße 30, 63911 Klingenberg
declares as the manufacturer the accuracy of the following information.
1. General information
Permissible options
T32.1S.xxx-S / T32.3S.xxx-S (xxx = 000/0IS/0NI)
Safety-relevant output signal
4 … 20 mA
Error current
Adjustable: ≤ 3.6 mA and ≥ 21.0 mA
(Factory settings: 3.5 mA and 21.5 mA to NAMUR
NE43)
Evaluated measurands /function
Temperature in °C, °F, K, R
Safety function
Single sensor
Duplex sensor, Redundant, Minimum value,
Maximum value, Average value
Device type per IEC 61508-2
B (complex components)
Operating mode
Low Demand Mode
Current hardware version
6
Current software version (Firmware)
2.2.1
Safety handbook
Issue 05/2010
Type of evaluation
Complete evaluation, in parallel with development,
of hardware and software incl. FMEDA on a
component level and change process to
IEC 61508-2,3
Evaluation through Report No.
TÜV Rheinland 968/EL 632.01/10
Test documents
Safety-Product Requirement Specification
Product Requirements Specification
Functional Safety Management Plan
Product verification plan
Data Sheet TE 32.04
FMEA at component level
Safety handbook
2. SIL Integrity
Systematic safety integrity
SIL3-capable software
Integrity against "random, dangerous
hardware errors"
(Type B components)
Single channel operation (HFT = 0, e.g. 1v1); SIL2
Two channel operation SIL3: to IEC 61508-6 Annex D
must determine a β-factor for the two channel (redun-
dant) application, in order to incorporate the 'Common
Cause Failure Probability'.
For further information, see WIKA contact data
Appendix 1: SIL Declaration of Conformity
Page 1/3