Technical data and intended use – WIKA DPGS43HP.160 User Manual

Page 5

background image

Pressure ranges

Working pressure max.

(static pressure)

Standard Option

Overpressure safety, single,

dual or alternating sides

Standard Option

0 ... 16 to 0 ... 40 mbar

.5

6

.5

-

0 ... 60 to 0 ... 50 mbar 6

10

.5

6

0 ... 400 mbar

5

40

4

40

0 ... 0.6 bar

5

40

6

40

0 ... 1 bar

5

40

10

40

0 ... 1.6 bar

5

40

16

40

0 ... .5 to 0 ... 5 bar

5

40

5

40

WIKA Operating instructions pressure gauges Model 7 with 831 per ATEX

5

080

50 07/

009 GB/D/F

GB

3. Technical data and intended use

3. Technical data and intended use

Pressure limitation

Model 73X.51/31: Steady:

full scale value

Fluctuating: 0.9 x full scale value

Table 1: Max. working pressure / Overpressure safety maximum in bar

Model 73X.14: Steady:

full scale value

Fluctuating:

0.9 x full scale value

Overpressure safety: 40, 100; 50 or 400 bar

Process connection

In accordance with the general technical regulations for pressure gauges

(i.e. EN 837-2 „Selection and installation recommendations for pressure
gauges“).

When screwing gauges in, the force required for this must not be applied
through the case, but rather through the spanner flats (using a suitable tool)
provided for this purpose on the square shaft of standard connections.

Temperature effect

When the temperature of the measuring system deviates from the reference
temperature (+0 °C): max. ±0.5 %/10 K of full scale value

IP Ingress protection

IP 54 per EN 60 59 / IEC 60 59
(with liquid filling IP 65)