NOTe: MINIMUM CLeARANCe FOR
SINgLe WALL STOVePIPe IS 18 INCHeS.
FOR DVL PIPe, THe MINIMUM IS 8
INCHeS.
exTeND-A-CAP ASSeMbLY
MINIMUM
CLeARANCe:
(NOTe beLOW)
COMbUSTIbLe WALL
THIMbLe ASSeMbLY
PIPe (AS ReqUIReD)
RIgID PIPe
SPACeR
RIgID Tee
ACCeSS DOOR
(FOR CLeANINg)
1 INCH AIR gAP
10
Adjustable Sleeve until the base of the Wall
Pass Through is flush against the masonry
(Fig.17) NOTE: The Wall Pass Through
must protrude a minimum of 2" into the
room (Fig.16).
Attach the 10" Long Rigid Pipe Section to the
front of the Wall Pass Through with four sheet
screws through the L-brackets (Fig.15, Fig.16)
Position the appliance, at it’s final location.
STEP FOUR: Push the Adjustable Sleeve from
the Wall Pass Through into the branch of the
tee. Connect Adjustable Sleeve to Tee branch
with the pre-formed buttons. Recommended
to grout in place with a high temperature grout
(Fig.15, Fig.16).
STEP FIVE: Slide the Wall Pass-Through
through the square trim plate and into the