Installation instructions, Prepare strike wiring – HES HT1006 User Manual
Page 3

Installation Instructions
3
Voltage: 12-24VDC
(11-28VDC range) operation
Filtered and Regulated Power Supply
Current: .
5 Amp Seated
.04 Amp Unseated
PIN 1 Black (0 VDC)
PIN 3 White (CANbus)
PIN 5
PIN 7 Brown (CANbus)
PIN 8
PIN 6
PIN 4
PIN 2 Red (+12 – 24 VDC)
-)]
NOTE:
For HT1006 (On the 8-Pin Connector):
PIN 2 Red (Power +12 - 24VDC)
PIN 1 Black [Power 0 VDC/Common(-)]
PIN 3 White CAN bus HIGH
PIN 7 Brown CAN bus LOW
endly with quick
cable lengths to a minimum.
.
The System is designed to be installation friendly with quick
connectors.
The total length of the bus should not be more then 50 meters
(164 feet) and stub (star) connections should not be more then
10 meters (33 feet). The optimal solution places the door
controller close to the door to keep cable lengths to a minimum.
IMPORTANT:
ElectroLynx connectors plug and lock together in only one way,
as shown.
Do NOT force connectors together.
Prepare Strike
Wiring
The HT1006 series drawing below show the Hi-O application
A. Electrolynx Connectors
B. Electrolynx Connector System Notes